GE F650 User Manual page 44

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

2.5 TECHNICAL SPECIFICATIONS
2.5.1.22 OVERFREQUENCY (81O)
Pickup level
Dropout level
Level accuracy
Trip delay
Reset delay
2
Minimum voltage threshold
Time Delay Accuracy
Operate time
Snapshot Events
2.5.1.23 FORWARD POWER (32FP)
Current, Voltage
Number of stages
Pickup level (two stages)
Dropout level
Level accuracy for primary magnitudes
Trip delay (two stages)
Timing accuracy
Block Time after close
Snapshot Events
2.5.1.24 DIRECTIONAL POWER (32)
Current, Voltage
Number of stages
Pickup level (two stages)
Characteristic Angle (two stages)
Accuracy for primary magnitudes
Trip delay (two stages)
Timing accuracy
Block Time after close
Snapshot Events
Operate time:
2-16
20.00 to 65.00 Hz in steps of 0.01 Hz
Pickup - 0.03 Hz
±0.05 Hz of the reading from 30 to 80 Hz
0.00 to 900.00 s. in steps of 0.01 s
0.00 to 900.00 s. in steps of 0.01 s
10 to 300V in steps of 1 V
0 to 7 cycles
Typically 10 cycles at 0.1 Hz/s change
Selectable by setting
Fundamental Phasor (primary values)
2
0.00-10000.00 MW in steps of 0.01 MW
97% to 98% of the pickup level
±3% complete range.
0.00 to 900.00 s in steps of 0.01 s
±3.5% of operate time or 50 ms. (whichever is greater)
0.00 to 900.00 s in steps of 0.01 s
Selectable by setting
Fundamental Phasor (primary values)
2
-10000.00 to 10000.00 MW (primary values) in steps of
0.01 MW
0.00 to 359.99 in steps of 0.01
±3% complete range
0.00 to 900.00 s in steps of 0.01 s
±3.5% of operate time or 50 ms. (whichever is greater)
0.00 to 900.00 s in steps of 0.01 s
Selectable by setting
< 45 ms at 50 Hz, typically
F650 Digital Bay Controller
2 PRODUCT DESCRIPTION
GEK-113000AE

Advertisement

Table of Contents
loading

Table of Contents