User-Programmable Elements - GE F650 User Manual

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
2.5.4.1 PLC LOGIC
Programming language:
Lines of code for versions previous to
7.00:
Lines of code for version 7.00 or newer:
(*) Note: Reserved Modbus memory space of PLC equations in text format is up to 15360 bytes. This space is shared with
information configured in Enervista at Setpoint> Relay Configuration. According to this, number of PLC equations could
be limited by values configured on that section.
Supported operations:
Libraries:
Inputs:
Number of timers:
2.5.4.2 FLEXCURVES
Number:
Reset points:
Operate points:
Time delay:
Saturation Level
2.5.4.3 USER-PROGRAMMABLE LEDS
Number:
Programmability:
Reset mode:
Reset Signal:
GEK-113000AE
The logical configuration is performed using graphical functions based on the
IEC 61131-3 standard.
Up to 640 lines of code or 15360 bytes whichever is greater (*)
Up to 1000 total equations or 15360 bytes whichever is greater (*)
NOT, XOR, OR (2 to 8 inputs), AND (2 to 8 inputs), NOR (2 to 8 inputs),
NAND (2 to 8 inputs), Latch (Reset Dominant), Edge Detectors, Timers.
2 inputs default gates, from 3 to 8 inputs provided in library format.
Starting in version 7.20, analog operators are also available.
Logical gates fully programmable by user. To create user-programmable logic
to be distributed as a single object.
Any logical variable, contact or virtual input
8 maximum in each logic scheme (provided in library format)
4 (A through D)
40 (0 through 1 of pickup)
80 (1 through 20 of pickup)
0 to 65535 ms in steps of 1
20 times the pickup level
15 configurable LEDs plus a ready non configurable LED
from any logical variable, contact, or virtual input
Self-reset or Latched.
The first 5 LED's are latched by hardware (red color ones), usually configured for
trip signals.
The following 10 ones (yellow and green) are self-reset but can be latched
through PLC configuration.
The LED's can be reset by hardware, pressing the front "esc" key during more
than 3 seconds or using the LED reset signal through PLC configuration.
F650 Digital Bay Controller
2.5 TECHNICAL SPECIFICATIONS

2.5.4 USER-PROGRAMMABLE ELEMENTS

2
2-25