APPENDIX D
SETPOINT > PRODUCT SETUP > MODBUS USER MAP
SETTING DESCRIPTION
Address 00 for Modbus user map
Address 01 for Modbus user map
Address 254 for Modbus user map
Address 255 for Modbus user map
SETPOINT > PRODUCT SETUP > FAULT REPORT
SETTING DESCRIPTION
Function permission
Positive sequence impedance module Pos Seq Module
Positive sequence impedance angle
Zero sequence impedance module
Zero sequence impedance angle
Line length
Display fault on HMI
Snapshot Event generation
CT Direction
SETPOINT > PRODUCT SETUP > OSCILLOGRAPHY
SETTING DESCRIPTION
Function Permission
Prefault
Samples per cycle
Maximum number of oscillos
Automatic oscillography overwrite
Snapshot Event generation
SETPOINT > PRODUCT SETUP > DATA LOGGER
SETTING DESCRIPTION
Function permission
Data logger Rate
Data Logger analog channels X
GEK-113000AE
NAME
DEFAULT VALUE
Address 00
0
Address 01
0
...
...
Address 254
0
Address 255
0
NAME
DEFAULT VALUE
Function
DISABLED
3.00
Pos Seq Angle
75
Zero Seq Module
9.00
Zero Seq Angle
75
Line Length
100.0
Show Fault On HMI
DISABLED
Snapshot Events
ENABLED
CT Direction
REVERSE
NAME
DEFAULT VALUE
Function
ENABLED
Trigger Position
30
Samples/Cycle
64
Max. Number Osc.
4
Automatic Overwrite
DISABLED
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Data Logger Rate
1 s
Data Logger Chnl X
None
F650 Digital Bay Controller
D.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
N/A
[0000 : FFFF]
N/A
[0000 : FFFF]
...
N/A
[0000 : FFFF]
N/A
[0000 : FFFF]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 Ohm
[0.01 : 250.00]
1 Deg
[25 : 90]
0.01 Ohm
[0.01 : 750.00]
1 Deg
[25 : 90]
0.1
[0.0 : 2000.0]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
NA
REVERSE; FORWARD
STEP
RANGE
N/A
[DISABLED – ENABLED]
1%
[5 : 95]
N/A
[4 – 8 – 16 –32 – 64]
1 oscillo
[1 : 20]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
[1 s, 5 min, 10 min, 15 min,
N/A
20 min, 30 min, 60 min.]
N/A
[1 to 16]
USER
VALUE
USER
VALUE
USER
VALUE
USER
VALUE
D
D-11