GE F650 User Manual page 90

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

3.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
Frequency and miscellaneous menu will be available at Protection Element section only for firmware version 7.50 or above.
FREQUENCY
MISCELLANEOUS
3.1.8.5 CONTROL ELEMENTS
3
This option shows all the control elements available in the relay as shown in Table 3.13: and Table 3.14:. Some of the
elements are grouped ones such as underfrequency, overfrequency and broken conductor. Users should take into account
that position of different Enervista 650 PC Menus could vary depending on relay firmware version.
Table 3.13: GENERAL OVERVIEW OF CONTROL ELEMENTS MENU FOR FIRMWARE VERSION BELOW 7.50
CONTROL
ELEMENTS
3-24
Underfrequency
Underfrequency unit (81U).
Overfrequency
Overfrequency unit (81O).
Frequency Rate of
Frequency rate of change function (81R).
change
Broken or fallen conductor detection function (I2/I1). Grouped element.
Ratio between the negative sequence current, I2, and the positive
Broken conductor
sequence current I1. In normal and balanced load situations, this ratio is
zero, while in severe load fault conditions, an unbalance is produced and
this ratio is increased.
Locked Rotor
Locked rotor detection function (48).
Load Encroachment
Load Encroachment function.
F650 units incorporate a flexible grouping capability for protection units.
This means that protection units can be used in either single setting
group (default mode-all units can operate simultaneously) or three
setting groups (in this mode, protection units are grouped in three
independent tables, with only one of them active at a given time).
Setting Group
Protection element grouping involves only Protection elements together
with broken conductor detection and over and under frequency, which
are usually considered as control elements. The rest of control elements
such as recloser, fuse failure, breaker failure, synchronism, and breaker
settings are not involved in the tabled groups concept.
Underfrequency
Underfrequency unit (81U). Grouped element
Overfrequency
Overfrequency unit (81O). Grouped element
Synchrocheck
Synchronism check unit (25). Not grouped, a single unit provided
Autoreclose
Recloser (79). Not grouped, a single unit provided
Breaker Failure
Breaker failure (50BF). Not grouped, a single unit provided.
VT Fuse Failure
Fuse Failure (VTFF). Not grouped, a single unit provided.
Broken or fallen conductor detection function (I2/I1). Grouped element.
Ratio between the negative sequence current, I2, and the positive
Broken Conductor
sequence current I1. In normal and balanced load situations, this ratio is
zero, while in severe load fault conditions, an unbalance is produced and
this ratio is increased.
Locked Rotor
Locked rotor detection function (48). Grouped element.
Pulse Counters
Pulse counters function. 8 counters provided.
Analog Comparators
Analog comparator function. 20 analog comparators provided.
Frequency rate of
Frequency rate of change function (81R).Grouped element.
change
Load Encroachment
Load Encroachment function. Grouped element.
Max. Number of Starts
Maximum Number of Starts (66). Not grouped, a single unit provided.
Digital Counters
Up to 8 Digital Counters
F650 Digital Bay Controller
GEK-106310AE