GE F650 User Manual page 300

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

APPENDIX D
SETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > GROUND IOC
GROUND IOC 1> GROUND IOC 2 > GROUND IOC 3
SETTING DESCRIPTION
Function permission
Input type
Pickup level
Trip time
Reset time
Snapshot event generation
SETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > GROUND DIRECTIONAL >
GROUND DIRECTIONAL 1> GROUND DIRECTIONAL 2 > GROUND DIRECTIONAL 3
SETTING DESCRIPTION
Function permission
Maximum Torque Angle
Operation Direction
Polarization type
Block logic type
Polarization voltage threshold
Snapshot event generation
SETPOINT > PROTECTION ELEMENTS > SENSITIVE GROUND CURRENT > SENSITIVE GROUND TOC
SENSITIVE GROUND TOC 1> SENSITIVE GROUND TOC 2 > SENSITIVE GROUND TOC 3
SETTING DESCRIPTION
Function permission
Input type
Pickup level
Curve shape
Time Dial
Reset type
Snapshot Event generation
GEK-113000AE
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Pickup Level
30.00
Trip Delay
0.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
MTA
-45
Direction
FORWARD
Polarization
VO
Block Logic
PERMISSION
Pol V Threshold
10
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Pickup Level
0.050
Curve
IEEE Ext Inv
TD Multiplier
1.00
Reset
INSTANTANEOUS
Snapshot Events
ENABLED
F650 Digital Bay Controller
D.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
0.01 A
[0.05 : 160.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 Deg
[-90 : +90]
N/A
[FORWARD – REVERSE]
[V
– I
– V
+I
– V
N/A
0
P
0
P
0
N/A
[BLOCK – PERMISSION]
1 V
[0 : 300]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
0.001 A
[0.005 : 16.000]
N/A
[See list of curves]
0.01 s
[0.00 : 900.00]
[INSTANTANEOUS –
N/A
LINEAR]
N/A
[DISABLED – ENABLED]
USER
VALUE
USER
VALUE
*I
]
P
USER
VALUE
D
D-19

Advertisement

Table of Contents
loading

Table of Contents