SETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>
DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3
SETTING DESCRIPTION
Function permission
Block from off-line
Directional Angle for stage 1
Pickup level for stage 1
Trip time for stage 1
Directional Angle for stage 2
Pickup level for stage 2
Trip time for stage 2
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS > POWER
WATT GND FLT HIGH 1> WATT GND FLT HIGH 2 > WATT GND FLT HIGH 3
WATT GND FLT LOW 1> WATT GND FLT LOW 2 > WATT GND FLT LOW 3
SETTING DESCRIPTION
Function permission
Supervision minimum voltage
Source of operating current.
Pickup Level for Overcurrent
Pickup Delay for Overcurrent
Pickup Level for operating Power
Max torque angle
Pickup Delay for Operating Power
Curve shape
Multiplier
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION
Setting Grouping Permission
Active Group
Snapshot Event generation
SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCY
UNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3
SETTING DESCRIPTION
Function permission
Pickup level
Trip time
Reset time
Minimum voltage threshold
Snapshot event generation
GEK-113000AE
NAME
DEFAULT VALUE
Function
DISABLED
Blk Time After Close
0.00
Dir Power Angle 1
0.00
Stage 1 Tap
10.00
Stage 1 Time
60.00
Dir Power Angle 2
0.00
Stage 2 Tap
20.00
Stage 2 Time
60.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Voltage Pickup Level
2
Current selection
IN
OC Pickup Level
0,005
OC Pickup Delay
0,2
Power Pickup
0,01
MTA
0
Power Pickup Delay
0,2
Curve
DEFINITE TIME
Multiplier
1
Snapshot Event
DISABLED
NAME
DEFAULT VALUE
Function
DISABLED
Active Group
GROUP 1
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
49.50
Trip Delay
0.00
Reset Delay
0.00
Minimum Voltage
30
Snapshot Events
ENABLED
F650 Digital Bay Controller
D.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 s
[0.00 : 900.00]
0.01 Deg
[0.00 : 359.99]
0.01MW
[-10000.00 : 10000.00]
0.01 s
[0.00 : 900.00]
1 Deg
[0.00 : 359.99]
0.01MW
[-10000.00 : 10000.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED-ENABLED]
0.01 V
[2.00 : 70.00]
N/A
[IN-IG]
0.001A
[0.005 : 0.400]
0.01 s
[0.00 : 600.00]
0.01 W
[0.01 : 4.50]
1 Deg
[0 : 360]
0.01 s
[0.00 : 600.00]
N/A
[DEFINITE TIME -
INVERSE TIME - USER
CURVE A - USER CURVE
B - USER CURVE C -
USER CURVE D]
0.01 s
[0.02 : 2.00]
N/A
[DISABLED-ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
[GROUP 1 – GROUP 2 –
N/A
GROUP 3]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 Hz
[20.00 : 65.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
1 V
[10 : 300]
N/A
[DISABLED – ENABLED]
USER
VALUE
USER
VALUE
USER
VALUE
D
USER
VALUE
D-23