GE F650 User Manual page 59

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
Protocols available:
Typical distance:
Isolation:
CAN PORT:
Rear port:
Type:
Fiber Wave length:
Fiber type:
Maximum recommended length
Isolation:
ETHERNET PORT:
Rear port:
For models B, C, D, E
For models G,H,J,K,L,M
Type (depending on model):
Model B:
Model C:
Model D:
Model E:
Model G:
Model H:
Model J:
Model K:
Model L:
Model M:
NOTE: (*) This Ethernet port (ETH_E) is intended only for maintenance purpose.
10/100BaseTX
100BaseFX
Wave length:
Fiber type:
Protocols available:
Typical distance:
Response time to ModBus commands:
Isolation:
In Models C and D, the 10/100BaseTX port is selected by an internal switch (see 3.3.3)
Two witness LED's for transmission and reception are included
SIMPLE NETWORK TIME PROTOCOL (SNTP)
Clock synchronization error:
PRECISION TIME PROTOCOL (PTP)
PTP IEEE Std 1588 2008 (version 2)
Power Profile (PP) per IEEE Standard PC37.238TM2011
Slave-only ordinary clock
GEK-113000AE
®
ModBus
RTU / DNP 3.0/IEC103
1200 m for cooper cable, 1000 m for glass fiber and 50 m for
plastic fiber
2 kV
CAN port in models C, M, X, Y, Z for asynchronous rear ports
Multimode glass F.O. port with ST connectors
820 nm
multimode 62.5/125 μm or 50/125 μm
300m for cooper cable and glass fiber
2 kV
ETH_1/ ETH_2
ETH_E/ ETH_A/ ETH_B
10/100BaseTX self-negotiable
10/100BaseTX + 100Base FX
10/100BaseTX + redundant 100BaseFX (Physical media redundancy)
Redundant 10/100BaseTX self-negotiable ports
1588, 10/100 Base TX* + 100 Base TX
1588, 10/100 Base TX* + 100 Base FX
PRP, 1588, 10/100 Base TX* + Redundant 100 Base FX
PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base FX
PRP, 1588, 10/100 Base TX* + Redundant 100 Base TX
PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base TX
RJ45 connector
ST connectors
1300 nm
multimode 62.5/125 . m or 50/125 . m
ModBus® TCP/IP
DNP over TCP/IP and UDP/IP
IEC 61850
Http, ftp, tftp (allow the use of a standard Internet browser)
1000 m for glass fiber and 150 m for RJ45 cable
10 ms Typical
2 kV
<10 ms (typical)
F650 Digital Bay Controller
2.5 TECHNICAL SPECIFICATIONS
2
2-31

Advertisement