APPENDIX B
B.1 PRP AND HSR ETHERNET PROTOCOLS
PRP can be enabled in configuration through a setting available on the network configuration menu (Product Setup?
Communication Settings? Network (Ethernet), REDUNDANCY, which already has the capability of enabling Failover
redundancy. When REDUNDANCY is set to PRP, the ports dedicated for PRP will operate in redundant mode.
The rights associated with configuring PRP follow the security requirements for network configuration.
PRP management through SNMP MIB is not supported, as F650 doesn't currently support SNMP for configuration.
Settings and actual values are only available through the front panel and through EnerVista.
The PRP solution to implement must ensure that performance requirements stated in IEC 61850-5 Clause 13 are still met.
It is specified under Clause 13 (Message performance requirements) that messages of type 1A must meet the performance
class P2/3, which is 3ms (See 3.7.1.1).
B
GEK-113000AE
F650 Digital Bay Controller