5.1 UPGRADE FROM VERSION BELOW V7.00.
RELAYS WITH FIBER OPTIC ETHERNET
The upgrade of the boot program (BOOTCODE) must be performed by crossed Ethernet copper cable connected to the
PC. It is not necessary to change the internal switch from fiber to RJ45, because the upgrade is made at 10Mb/s.
This does not apply to the firmware upgrade, which can be done either via Ethernet Fiber connection, or through the
RJ45 cable connection.
For upgrading firmware versions lower than 3.20 or upgrading bootware, be aware to calibrate the unit offset, after
upgrading it, on Communication --> Calibration --> Offset Calibration . No analog currents nor analog voltages must be
injected in the unit during this process.
1.
Ethernet Connection/Type - Both boot code and firmware upgrade processes require Ethernet communications. It is
strongly recommended to use a direct connection between the PC and the relay using a Cross-Over RJ45 Ethernet
cable, instead a direct connection through a hub or switch. Upgrading through Local Area Network (LAN) must be
avoided.
Serial RS232 Communication - Serial communication is necessary only to perform the bootware upgrade for versions
previous to 7.00.
2.
Relay IP Address - And IP address must be assigned to the relay in the Ethernet parameters via HMI at PRODUCT
SETUP>COMMUNICATION>ETHERNET>ETHERNET1 menu or via Enervista 650 Setup at SETPOINT>PRODUCT
SETUP>COMMUNICATION SETTINGS>NETWORK (Ethernet) 1 as shown in the table below:
Table 5–1: ETHERNET PARAMETERS
PRODUCT SETUP>COMMUNICATION SETTINGS >NETWORK (ETHERNET) 1
NAME
IP Address Oct1
IP Address Oct2
IP Address Oct3
IP Address Oct4
Netmask Oct1
Netmask Oct2
Netmask Oct3
Netmask Oct4
Gateway IP Oct1
Gateway IP Oct2
Gateway IP Oct3
Gateway IP Oct4
3.
PC IP Address - In case the boot code has been previously updated to the relay (section 9.2), the IP address and other
parameters already assigned in the process will be:
5
IP Address:192.168.37.177
Netmask:255.255.255.0
Gateway:192.168.37.10
Then the PC settings should be the same pattern as follows:
5-2
5 BOOTCODE AND FIRMWARE UPGRADE
VALUE
UNITS
192
168
37
177
255
255
255
0
192
168
37
10
F650 Digital Bay Controller

5.1.1 COMMUNICATION PARAMETERS