5.2 FIRMWARE UPGRADE VERSION V7.00 OR HIGHER
When upgrading the firmware the entire settings and relay configuration are reset to factory default values. Then the User
is committed to download the settings, configuration and logic files to the relay in order to get it fully operative.
Calibration settings and configuration must be loaded to the relay once the upgrade process has finished.
To recover and download the different files to the relay use Enervista 650 Setup and at the top menu bar choose:
COMMUNCATION>CALIBRATION>SET CALIBRATION FILES: to restore in the relay the calibration settings if
necessary.
FILE>CONFIG FILE (*.650) Converter: to convert the setting and configuration file *.650 for the relay (if it was in a
previous version format).
FILE>SEND INFO TO RELAY: to send the new settings and configuration file to the unit.
5.2.3.3 ORDERING CODE UPGRADE PROCESS
In case special functionality model (or a new order codes required by customer) with password requirement (see model
selection), the program will request a password to continue.
1-
With the purpose of reaching the window where the password is requested, the user must be communicating to
the relay (ONLINE MODE). On the menu "File" the following submenu will be available (for firmware versions
>=700):