GE F650 User Manual page 88

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

3.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
3.1.8.3 BREAKER
This section shows the settings related to the Breaker definition such as shown in the following table
Table 3.9: GENERAL OVERVIEW OF BREAKER MENU
Breaker settings
Breaker maintenance
3.1.8.4 PROTECTION ELEMENTS
This option shows all the protection-grouped elements available in the relay as shown in Table 3.10: or Table 3.11: (depend
on firmware version). Each of these groups includes the specific protection units of the same type. For example phase
currents group includes TOC, IOC, directional units, etc. There are three groups available, so there are three protection
3
units of each function that can work in grouped mode or ungrouped (altogether). Users should take into account that
position of different Enervista 650 PC Menus could vary depending on relay firmware version.
Table 3.10: GENERAL OVERVIEW OF PROTECTION ELEMENTS MENU FOR FIRMWARE VERSION BELOW 7.50
PROTECTION
ELEMENTS
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
Table 3.11: GENERAL OVERVIEW OF PROTECTION ELEMENTS MENU FOR FIRMWARE VERSION 7.50 OR ABOVE
PROTECTION
ELEMENTS
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
3-22
Breaker settings, maintenance and switchgear selection of the device
configured as breaker in the F650. The selected switchgear will be used
in recloser, breaker failure and synchronism functions. The settings are
Number of Switchgear, Maximum KI2t, KI2t Integ. Time, Maximum
Openings, Max.Openings 1 hour and Snapshot Events.
These settings correspond to the initialization of (KI)
counting of number of openings and closings of the switchgear
configured as breaker. These Counters allow the breaker Maintenance.
They are used to cumulate the breaker ageing produced by a trip or a
breaker opening. In order to incorporate the breaker historic, in case of
existing breakers, the system allows assigning an initial value to
accumulated amperes, and to the number of opening and closing
operations.
Phase Current
All overcurrent grouped functions for phase current.
All overcurrent grouped functions for neutral current. (Calculated from
Neutral Current
phases, not measured)
All overcurrent grouped functions for ground current. (Measured from 4th
Ground Current
current input)
Sensitive Ground
All overcurrent grouped functions for sensitive ground current.
Current
(Measured from 5th current input)
Negative Sequence
All Negative sequence overcurrent grouped functions.
Current
All voltage grouped functions for phases, neutral, ground and auxiliary
Voltage Elements
voltage
Forward power, directional power and wattmetric ground fault (High and
Power
Low) grouped protection functions.
All protection functions that could be available when setting group 1 the
Setting Groups 1
active group
All protection functions that could be available when setting group 2 the
Setting Groups 2
active group
All protection functions that could be available when setting group 3 the
Setting Groups 3
active group
All protection functions that could be available when setting group 4 the
Setting Groups 4
active group
All protection functions that could be available when setting group 5 the
Setting Groups 5
active group
All protection functions that could be available when setting group 6 the
Setting Groups 6
active group
F650 Digital Bay Controller
2
t counters, and the
GEK-106310AE