6 COMMISSIONING
Percent of Load-to-Trip
The relevant actual values displays are shown below:
ACUAL -> METERING -> PRIMARY VALUES -> CURRENT -> % OF LOAD-TO-TRIP
Note
Percent of load-to-trip is calculated from the phase with the highest current reading. It is
the ratio of this current to the lowest pickup setting among the phase time and instantaneous overcurrent protection
features. If all of these features are disabled, the
value displayed will be "0".
- Inject current of various values into Phase A.
- Verify that percent load-to-trip is calculated as the correct
percentage of the most sensitive operational Phase Overcurrent
element and displayed.
- Repeat for phases B and C.
Equations to be applied for powers in a wye connection are as follows:
Apply the following current and voltage values:
APPLIED VOLTAGE AND CURRENT VALUES PER PHASE
PHASE A
VI = 50 V, 0º
Ia = 10∠45º
With the indicated voltage and current values, verify that the power measure corresponds to expected values indicated in
the following table:
EXPECTED POWER VALUES
PHASE A
Pa = 353.55 MW
Qa = 353.55 MVAr
Maximum admissible error is ± 1% of the test value for P and Q, and 0.02 for cosj.
Frequency measure on channel VII (terminals A7-A8):
Apply 50 Vac at 50 Hz on channel VII. Maximum admissible error:± 10 mHz.
Apply 50 Vac at 60 Hz on channel VII. Maximum admissible error: ± 12 mHz.
Frequency measure on channel Vx (terminals A11-A12):
GEK-113000AE
POWER PER PHASE
P=V*I*Cosϕ
Q=V*I*Senϕ
PHASE B
VII = 50 V , 120º
Ib= 10∠165º
PHASE B
Pb = 353.55 MW
Qb = 353.55 MVAr
F650 Digital Bay Controller
6.8 VERIFICATION OF MEASUREMENT

6.8.3 ACTIVE, REACTIVE POWER, AND COSJ METERING

THREE-PHASE POWER
P=Pa+Pb+Pc
Q=Qa+Qb+Qc
PHASE C
V-I ANGLES
VIII = 50V, 240º
ϕ=45º
Ic = 10∠285º
Cosϕ= 0.707
PHASE C
THREE-PHASE
Pc = 353.55 MW
P = 1060.66 MW
Qc = 353.55 MVAr
Q = 1060.66 MVAr

6.8.4 FREQUENCY