12.8.2

P564 Batch Setpoint

Sets the batch total. When the amount of material delivered reaches this point, the batch relay
contact opens (P100) to signal the end of the batch. (
Enter the setpoint of the units of weight selected (P005).
Note
The batch setpoint can be modified while in RUN mode using the up/down arrow keys.
12.8.3

P566 Batch Pre-Warn

Enables or disables the pre-warn function associated with batch control, warning that the batch
is nearing completion.
Entry:
0 =OFF
1 = ON
12.8.4

P567 Batch Pre-Warn Setpoint

Sets the setpoint for the pre-warn function (P566). When the batch reaches the setpoint, the
relay contact associated with the pre-warn function (P100) closes (
Enter setpoint in units of weight selected (P005).
12.8.5

P568 Batch Pre-Act

Acts on the batch operation such that when the batch totalizer is reset, the batch total is
compared to the setpoint (P564). The difference is then applied to pre-act on the setpoint for the
next batch to improve the accuracy of the batch. The activity is internally limited to ±10% of the
batch setpoint.
Entry:
0 = OFF
1 = Auto
2 = Manual
e.g. For Auto Batch Pre-Act
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
f
f
1st batch
setpoint
pre-act
total
f
= 0.000).
2nd batch
1000
1000
1000
1050
12.8 Batch Control (P560 – P568)
f
= 0.000).
3rd batch
1000
950
960
990
1000
Parameters
177