Error Code
The codes in this column with checkmarks will produce relay output for a diagnostic alarm.
a)
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
! a)
240
241
242
243
244
PF
Code Name
Integrator not config-
ured
No PID mA Input
No PID mA Output
No batch setpoint relay
No speed relay
Power Failure
Troubleshooting
13.2 Specifically
Message/Action
P002-P017 must be
programmed
PID Process Value
Source (P402) or PID
Setpoint (P414) has
been programmed for a
mA Input, however mA
Input Function (P255)
has not been pro-
grammed properly.
PID System (P400) has
been turned on, but mA
Output (P201) has not
been programmed
properly.
Batch has been set up,
but no relay has been
configured for a set-
point.
Second speed sensor
configured, but no relay
is assigned
Displayed at the bottom
right corner of the dis-
play if power is inter-
rupted after the
integrator has been
calibrated.