P408-01 Feed Forward Term
Enter
Enter the value for the feed forward term, for example: nominal value of 0.3.
P410-01 Manual Mode Output
Current Output Value
% value of output during manual operation, P400 = 1.
P414-01 Setpoint Configuration
0-Local, 1mA In
Selection of setpoint source: 0 = local (keypad or Dolphin Plus), 1 = mA input
Local: the setpoint is the value entered into P415
mA Input 1: the setpoint is the mA value on input 1, terminals 5 and 6 on the mA I/O board
mA Input 2: the setpoint is the mA value on input 2, terminals 7 and 8 on the mA I/O board
P415-01 Local Setpoint Value
Enter Setpoint
Enter the setpoint value in engineering units. Not applicable if P414 = 1.
P416-01 External Setpoint
Setpoint
Current setpoint value in engineering units, obtained from the mA input.
P418-01 Remote Setpoint Ratio
Enter % of Master Output
Increase or decrease to scale input setpoint if desired.
P250-01 mA Input Range
Select 1- 0 to 20, 2-4 to 20
Select the appropriate range for the mA input signal.
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
E
0.3
E
0
E
0
E
0
E
0
E
100.000
E
2
PID Control