12.6 Linearization Parameters (P390 - P392)

12.6
Linearization Parameters (P390 - P392)
These parameters are used to compensate for non-linear response of the weighing system to
the BW500 and BW500/L. Refer to
parameters.
Note
In the case of multispan operation, the linearizer is applied to all spans.
12.6.1

P390 Linearizer

Enables or disables the linearization function.
Entry:
0 = OFF
1 = ON
12.6.2

P391 Linearizer Load Points

Enters the load values, in units of P017, for the point selected, points 1 to 5 (P391-01 to -05) (
0.00, 150 % max.)
12.6.3

P392 Linearizer Compensation %

Enters the compensation value, in percent, for the point selected, point 1 to 5 (P392-01 to −05) (
= 0.00), range is -150 to 150 %.
12.6.4

P398-01 Moisture Content

Factors out moisture component of load, rate and total for all multispans selected. The factored
values are meant to report the dry mean values of the material being conveyed (
Enter the moisture content in % weight or mA Input Value
BW500/L will allow manual entry of a moisture content.
1)
12.6.5

P398-02 Moisture Content

Allows moisture content P398-01 to be scaled to maximum value.
Enter the moisture content in % weight (maximum value 20 mA)
Note
Not available with BW500/L.
172
f
Linearization
for execution, and example on the use of these
.
1)
Operating Instructions, 12/2016, A5E33482052-AD
f
=
f
f
= 0.00)
BW500 and BW500/L