CGC 400 DRH 4189340786 UK
Additional functions
In this example, inhibit is set to Not run status and GB ON. Here, the alarm will only be active when the gen-
erator is running and disabled again when the GB is closed.
7.5.1 Run status (6160)
Alarms can be adjusted to activate only when the running feedback is active and a specific time delay has
expired.
The diagram below illustrates that after activation of the running feedback, a run status delay will expire.
When the delay expires, alarms with Run status will be activated.
DEIF A/S
Page 53 of 96