Deif CGC 400 Reference Book page 36

Compact genset controller
Hide thumbs Also See for CGC 400:
Table of Contents

Advertisement

CGC 400 DRH 4189340786 UK
The sequence is shown in the diagram below.
Primary running
feedback
Secondary running
feedback
Start relay (crank)
Alarm
Interruption of start sequence
The start sequence is interrupted in the following situations:
Event
Stop signal
Start failure
Remove starter feedback
Running feedback
Running feedback
Running feedback
Running feedback
Running feedback
Running feedback
Emergency stop
Alarm
Stop push-button on display
Modbus stop command
Binary stop input
Deactivate the "auto start/stop" Auto mode in the following genset modes:
If the MPU input is to be used to remove the starter, it has to be set up in menu 6174.
Setpoints related to the start sequence
- Crank failure alarm (4530 Crank failure)
DEIF A/S
Running feedback failure
1sec
t
Alarm
Tacho setpoint.
Digital input.
Tacho setpoint.
W terminal
Frequency measurement above 18 Hz.
The frequency measurement requires a voltage measurement of 30% of
U
.
NOM
The running detection based on the frequency measurement can replace
the running feedback based on tacho or digital input or engine communi-
cation.
Oil pressure setpoint (menu 6175).
EIC (engine communication).
Alarms with shutdown" or "trip and stop" fail class.
Manual mode.
Manual mode.
Manual mode.
Island operation or load takeover mode.
Functional descriptions
Comment
Page 36 of 96