Fuel Fill Check - Deif CGC 400 Reference Book

Compact genset controller
Hide thumbs Also See for CGC 400:
Table of Contents

Advertisement

CGC 400 DRH 4189340786 UK
Parame-
Name
ter
6551
Fuel pump log.
start
6552
Fuel pump log.
stop
6553

Fuel fill check

6554
Output A
6555
Type
6556
Fail class
Setpoints available in menu 6550:
The fuel pump relay can be activated via M-Logic.
The output relay should be configured as a limit relay. Otherwise, an alarm will be raised when-
ever the output is activated.
The below drawing shows how the fuel pump is activated when the level reaches 20% and stopped again
when the level has reached 80%.
Fuel level
80%
20%
Fuel pump start level
7.14.1 Fuel fill check
The fuel pump logic includes a Fuel fill check function.
DEIF A/S
Fuel transfer pump start point in percentage.
Fuel transfer pump stopping point in percentage.
Delay timer before activating fuel fill check alarm.
The output relay to be used for control of the fuel pump. The selected relay
activates below the start limit and deactivates above the stop level.
The multi-input or external analogue input to be used for the fuel level sen-
sor.
Choose multi-input if 4-20 mA is used.
Choose "auto detection" if an RMI is used.
The fail class of the fuel fill alarm.
Fuel service tank level
Fuel pump stop level
Function
Time
Additional functions
Page 66 of 96