CGC 400 DRH 4189340786 UK
Running feedback
The diagram below shows how the running feedback is detected at the firing speed level. The factory setting
is 1000 RPM (6170 Running detect.).
RPM
RPM
NOM
Run. feedback,
menu 4301
Firing speed
Notice that the factory setting of 1000 RPM is higher than the RPM level of starter motors of
typical design. Adjust this value to a lower value to avoid damage of the starter motor.
Remove starter input
The drawing below shows how the setpoint of the remove starter is detected at the firing speed level. The
factory setting is 400 RPM (6170 Running detect.).
RPM
RPM
NOM
Run. feedback,
menu 4301
Remove starter,
menu 6161
Firing speed
The number of teeth on the flywheel must be adjusted in menu 6170 when the MPU input is
used.

7.1.4 Oil pressure

The multi-inputs on terminals 6, 7 and 8 can be used for the detection of running feedback. The terminal in
question must be configured as a RMI input for oil pressure measurement.
DEIF A/S
RPM
t
RPM
t
Running
Additional functions
Page 47 of 96