Analogue Tacho Feedback - Deif CGC 400 Reference Book

Compact genset controller
Hide thumbs Also See for CGC 400:
Table of Contents

Advertisement

CGC 400 DRH 4189340786 UK
RPM
RPM
NOM
Run. feedback
Firing speed
The diagram illustrates how the digital running feedback is activated when the engine has reached its firing
speed.
Remove starter
When the digital remove starter input is present, the start relay is deactivated, and the starter motor will be
disengaged.
RPM
RPM
NOM
Run. feedback
Remove starter
Firing speed
The diagram illustrates how the remove starter input is activated when the engine has reached its firing
speed. At the running speed, the digital running feedback is activated.
The remove starter input must be configured from a number of available digital inputs.
The running feedback is detected by either the digital input (see diagram above), frequency
measurement above 18 Hz, RPM measured by magnetic pick-up or EIC (engine communica-
tion).

7.1.3 Analogue tacho feedback

When a magnetic pick-up (MPU) is being used, the specific level of revolutions for deactivation of the start
relay can be adjusted.
DEIF A/S
RPM
t
RPM
t
Running
Additional functions
Page 46 of 96

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents