AGC 200 operators manual 4189340607
UK
4.1.5 Status line texts
Status text
BLOCK
SIMPLE TEST
LOAD TEST
FULL TEST
SIMPLE TEST ###.#min
LOAD TEST ###.#min
FULL TEST ###.#min
ISLAND MAN
ISLAND SEMI
READY ISLAND AUTO
ISLAND ACTIVE
AMF MAN
AMF SEMI
READY AMF AUTO
AMF ACTIVE
FIXED POWER MAN
FIXED POWER SEMI
READY FIXED P AUTO
FIXED POWER ACTIVE
PEAK SHAVING MAN
PEAK SHAVING SEMI
READY PEAK SHAV AU-
TO
PEAK SHAVING ACTIVE
LOAD TAKEOVER MAN
LOAD TAKEOVER SEMI
READY LTO AUTO
LTO ACTIVE
MAINS P EXPORT MAN
MAINS P EXPORT SEMI
READY MPE AUTO
MPE ACTIVE
DG BLOCKED FOR
START
GB ON BLOCKED
DEIF A/S
Condition
Block mode is activated
Test mode is activated
Test mode is activated and test timer counting down
Genset stopped or running and no other action tak-
ing place
Genset stopped in Auto
Genset running in Auto
Genset stopped or running and no other action tak-
ing place
Genset stopped in Auto
Genset running in Auto
Genset stopped or running and no other action tak-
ing place.
Genset stopped in Auto
Genset running in Auto
Genset stopped or running and no other action tak-
ing place.
Genset stopped in Auto
Genset running in Auto
Genset stopped or running and no other action tak-
ing place
Genset stopped in Auto
Genset running in Auto
Genset stopped or running and no other action tak-
ing place
Genset stopped in Auto
Genset running in mains power export mode
Generator stopped and active alarm(s) on the gener-
ator
Generator running, GB open and an active "Trip GB"
alarm
Display and menu structure
Comment
Page 14 of 24