The following adjustments must be made to make the system ready for the three-phase measuring (example
400/230V AC):
Setting
Adjustment
6004
G nom. voltage
6041
G transformer
6042
G transformer
6051
BB transformer
6052
BB transformer
6053
BB nom. voltage
The controller has two sets of BB transformer settings, which can be enabled individually in
this measurement system.

4.4 Applications

4.4.1 Applications and genset modes

This section about applications is to be used for reference using the particular genset mode as
starting point. It is not suitable for reading from beginning to end.
The unit can be used for the applications listed in the table below.
Automatic Mains Failure (no back sync.)
Island operation
Load takeover
Automatic Mains Failure (no back sync.)
Island operation
Load takeover
For a general description of the available running modes, please refer to the chapter "Running
mode description".

4.4.2 Application design

The application is designed through the utility software. Please select configuration.
DEIF A/S
Phase-phase voltage of the generator
Primary voltage of the G voltage transformer (if installed)
Secondary voltage of the G voltage transformer (if installed)
Primary voltage of the BB voltage transformer (if installed)
Secondary voltage of the BB voltage transformer (if installed)
Phase-phase voltage of the busbar
Application
Genset mode
Description
CGC 413
CGC 412/CGC 413
CGC 413
Running mode
Auto
Test
X
X
X
X
X
X
Functional descriptions
Adjust to
value
400V AC
U
NOM
U
NOM
U
NOM
U
NOM
U
NOM
Comment
Man
Block
X
X
X
X
X
X
Page 13 of 96