Standard Texts - Deif CGC 400 Reference Book

Compact genset controller
Hide thumbs Also See for CGC 400:
Table of Contents

Advertisement

CGC 400 DRH 4189340786 UK

7.23.1 Standard texts

Condition
BLOCK
SIMPLE TEST
FULL TEST
SIMPLE TEST ###.#min
FULL TEST ###.#min
ISLAND MAN
READY ISLAND AUTO
ISLAND ACTIVE
AMF MAN
READY AMF AUTO
AMF ACTIVE
LOAD TAKEOVER MAN
READY LTO AUTO
LTO ACTIVE
DG BLOCKED FOR
START
GB ON BLOCKED
SHUTDOWN OVER-
RIDE
ACCESS LOCK
GB TRIP EXTERNALLY
MB TRIP EXTERNALLY
IDLE RUN
IDLE RUN ###.#min
START PREPARE
START RELAY ON
START RELAY OFF
MAINS FAILURE
DEIF A/S
Comment
Block mode is activated
Test mode is activated
Test mode activated and test timer counting down
Genset stopped or running and no other action taking
place
Genset stopped in Auto
Genset running in Auto
Genset stopped or running and no other action taking
place
Genset stopped in Auto
Genset running in Auto
Genset stopped or running and no other action taking
place
Genset stopped in Auto
Genset running in Auto
Generator stopped and active alarm(s) on the genera-
tor
Generator running, GB open and an active "Trip GB"
alarm
The configurable input is active
The configurable input is activated, and the operator
tries to activate one of the blocked keys
Some external equipment has tripped the breaker
Some external equipment has tripped the breaker
The "Idle run" function is active. The genset will not
stop until a timer has expired
The timer in the "Idle run"' function is active
The start prepare relay is activated
The start relay is activated
The start relay is deactivated during the start se-
quence
Mains failure and mains failure timer expired
Additional functions
An external trip is log-
ged in the event log
An external trip is log-
ged in the event log
Page 85 of 96