IQ 100 Series (130/140/150) Meter
Overview &Specifications
Compliance
•
UL Listing: USL/CNL E185559
•
IEC 687 (0.5% Accuracy)
•
ANSI C12.20 (0.5% Accuracy)
•
ANSI (IEEE) C37.90.1 Surge Withstand
•
ANSI C62.41 (Burst)
•
IEC1000-4-2: ESD
•
IEC1000-4-3: Radiated Immunity
•
IEC1000-4-4: Fast Transient
•
IEC1000-4-5: Surge Immunity
Accuracy
Measured Parameters
Voltage L-N
Voltage L-L
Current Phase
Current Neutral (Calculated)
+/- Watts
+/- Wh
+/- VARs
+/- VARh
VA
VAh
PF
Frequency
% of Load Bar
*Accuracy stated for 5Amp secondary WYE or Delta connections. For 1Amp secondary or 2.5 element
connections, add 0.1% of Full Scale + 1 digit to accuracy specification.
16
User and Installation Manual IM02601003E-July 2010 www.eaton.com
Meter Accuracy by Measured Parameter
Accuracy % of Reading*
0.25%
0.25%
0.25%
2.0% F.S.
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
+/- 0.01 Hz
1-120%
Display Range
0-9999 V or kV Autoscale
0-9999 V or kV Autoscale
0-9999 V or kV Autoscale
0-9999 V or kV Autoscale
0-9999 Watts, kWatts, MWatts
5 to 8 Digits Programmable
0-9999 VARs, kVARs, MVARs
5 to 8 Digits Programmable
0-9999 VA, kVA, MVA
5 to 8 Digits Programmable
+/- 0.5 to 1.0
45 to 65 Hz
10 Segment Resolution Scalable