IQ 100 Series (130/140/150) Meter
Overview &Specifications

Utility Peak Demand (IQ140/150)

The IQ 100 Series meter provides user-configured Fixed Window or Sliding Window Demand. This
feature allows you to set up a Customized Demand Profile. Fixed Window Demand is demand used over
a user-configured demand period (usually 5, 15 or 30 minutes). Sliding Window Demand is a fixed
window demand that moves for a user-specified subinterval period. An example of Sliding Window De-
mand is a 15-minute demand using 3 subintervals and providing a new demand reading every 5 minutes,
based on the last 15 minutes.
Utility Demand Features can be used to calculate kW, kVAR, kVA and PF readings. All other parameters
offer Max and Min capability over the user-selectable averaging period. Voltage provides an Instanta-
neous Max and Min reading which displays the highest surge and lowest sag seen by the meter.

Specifications

Power Supply
·
Range:
·
Power Consumption:
Voltage Inputs (Measurement Category III)
·
Range:
·
Supported hookups:
·
Input Impedance:
·
Burden:
·
Pickup Voltage:
·
Connection:
·
Max Input Wire Gauge:
·
Fault Withstand:
·
Reading:
Current Inputs
·
Class 10:
·
Class 2:
·
Burden:
·
Pickup Current:
·
Connections:
·
Fault Withstand:
·
Reading:
14
User and Installation Manual IM02601003E-July 2010 www.eaton.com
1 Option: Universal, (90 to 265) VAC @50/60Hz or (100 to
370) VDC
4 Option: (18-60) VDC
5 VA, 3.5W
Universal, Auto-ranging up to 416Vac L-N, 721Vac L-L
3 Element Wye, 2.5 Element Wye, 2 Element Delta, 4 Wire
Delta
1M Ohm/Phase
0.0144VA/Phase at 120 Volts
10Vac
Screw terminal (Figure 3.4)
AWG#12 / 2.5mm2
Meets IEEE C37.90.1
Programmable Full Scale to any PT Ratio
5A Nominal, 10A Maximum
1A Nominal, 2A Maximum
0.005VA Per Phase Max at 11 Amps
0.1% of Nominal
O or U Lug Electrical Connection (Figure 3.1)
Pass-through Wire, 0.177" / 4.5mm Maximum Diameter
(Figure 3.2)
Quick Connect, 0.25" Male Tab (Figure 3.3)
100A/10sec., 300A/3sec ., 500A/1sec.
Programmable Full Scale to any CT Ratio