Eaton® PDI WaveStar Infinity 2 Monitoring System
Setup and Operation Manual
p/n: P-164001106
Revision 01

Advertisement

Table of Contents
loading

Summary of Contents for Eaton PDI WaveStar Infinity 2

  • Page 1 Eaton® PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual p/n: P-164001106 Revision 01...
  • Page 2 ToughRail Technology, and WaveStar are registered trademarks of Power Distribution Inc. All other trademarks are held by their respective owners. All other trademarks are property of their respective companies. ©Copyright 2023 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3 Dear Customer, On behalf of everyone at Eaton, we thank you for partnering with us, and trusting us to maintain your business continuity and preventing downtime at your facility. Our suite of backup power, power distribution and power management products are designed to protect you from a host of threats including power outages, surges, lighting strikes, and enable you to monitor and control your power infrastructure.
  • Page 5 5.2 Setup: GENERAL Screen..........................31 5.3 Setup: NETWORK/PROTOCOLS Screen......................35 5.4 Limits: Set Analog Alarm Values ........................43 5.4.1 Main Circuits and Subfeeds ........................44 5.4.2 Panelboard Circuits ..........................44 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 6: Table Of Contents

    8 8 B B i i b b l l i i o o g g r r a a p p h h y y ..........................................................6 6 7 7 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 7 Figure 36. Transformer Screen Digital Points....................48 Figure 37. Relay Screen ..........................49 Figure 38. HOME Screen ..........................51 Figure 39. HOME Screen with Cascading ......................52 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 8 Figure 44. Active Alarms vs. Alarm History ...................... 58 Figure 45. Log Events Screen ........................59 Figure 46. CT Fix Positions on Panelboard CT Strip .................... 63 viii Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 9 Table 4. Calibration Procedure with Calibrate Screen ..................61 Table 5. Inline Calibration Procedure ......................62 Table 6. Replacing a Failed Panelboard CT – Procedure ..................63 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 10 List of Tables Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 11 Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel and in accordance with all local safety codes. Eaton assumes no responsibility for any consequences arising out of the use of this manual.
  • Page 12 Safety Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 13 C C h h a a p p t t e e r r 2 2 I I n n t t r r o o d d u u c c t t i i o o n n The Eaton PDI Infinity 2 Monitoring Systems are high-performance monitoring systems for Eaton power distribution equipment and are customized for the underlying equipment configuration according to customer requirements.
  • Page 14 2 2 . . 2 2 W W a a r r r r a a n n t t y y To view the warranty please click on the link or copy the address to download from the Eaton website: Eaton Product Warranty https://www.eaton.com/content/dam/eaton/products/backup-power-ups-surge-it-power-distribution/backup-...
  • Page 15 The upstream Ethernet port can provide remote access to the monitor by one of the following methods: • Web Browser: Monitor can be accessed by using any web browser (Google’s Chrome browser is recommended), and the unit IP address. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 16 Infinity 2 Monitors have soft biasing (27K pull-up and pull-down resistors) on the + and – transmit and receive lines. Therefore, if the customer’s Modbus client device allows for control, Eaton recommends that the user turn on biasing and turn off termination, which may “fight” the biasing. Biasing the client device’s lines is not critical because the Infinity 2 Monitor is already biasing the lines.
  • Page 17 Pins 1 and 2 and a jumper on Pins 5 and 6. TX+, TX-, RX+, RX-, GND TX+, TX-, RX+, RX-, GND Modbus RTU Connection (Paralleled Connectors) Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 18 TX+ or RX+ on the Monitor (either one, because the on-board 2-wire jumpers short them together) wires to TX+ or RX+ on downstream devices. • TX- or RX- on the Monitor wires to TX- or RX- on downstream devices. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 19 Monitor 3 Client Device RX+/TX+  RX+/TX+  RX+/TX+  RX+/TX+ + and – wires should be in the RX-/TX- RX-/TX-  RX-/TX- RX-/TX- same shield.   Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 20 Customer Network Connections Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 21 Digital Inputs Option Board, monitoring up to (8) digital inputs, such as circuit breaker aux contacts and building alarms. • Relay Option Board with (4) relay outputs. Figure 5. Panelboard with Sensor CT Strips on Each Side Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 22 The physical network order of the boards is shown by the arrows in the following illustrations. When you have more than one sensor board of the same type, the network order of boards is important for identifying which board to connect to. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 23 The yellow arrow shows the network order of Sensor Boards in the Monitoring Compartment. The network order of sensor boards is followed in the Modbus point list, SNMP MIB, and Sensor Status screen. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 24 Optional Sensor Base is located on Monitor Board is located behind Sensor Combo Board side behind dead the Sensor Base Board on front panel. reverse side of panel. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 25 (1) Sensor Combo PowerPak 2 PDU PowerHub 2 PDU Board and up to (4) Sensor Board and up to (3) Sensor Combo Boards. Base Boards. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 26 The REPO connection on the VVIT Board is clearly marked. Figure 9. REPO Connection to VVIT Board VVIT Board The VVIT Board is typically the �irst PCB in a PDU’s sensor board chain. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 27 The only connections to Option Boards that customers usually make are to a Digital Inputs Option Board and a Relay Option Board. Digital Inputs and Relays are typically the last boards listed in the sensor chain. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 28: Digital Inputs Screen

    To test that your selected Digital Input sets the correct alarm, you can jumper the Digital Input. Check the Alarm Screen to see that the correct alarm is issued. Figure 11. Digital Inputs Option Board Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 29 D1-D8 correspond to the D1-D8 Unassigned digital inputs are named as Extra, connections on the Digital Inputs with its connection number in parentheses: Options board. Extra (D6) Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 30 Status screen as “Relay 1” and individual relays are listed as (Sensor Board Name/Relay Name): • Relay1 Relay 1 • Relay1 Relay 2 • Etc. See also Relay Screen, Figure Figure 13. Relay Option Board Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 31 Sensor Base Board layout: Options Boards are ordered by position number 1-4 on the Sensor Base Board (See paragraph 4.2.4 Sensor Base Boards and Option Boards, and Figure 10). Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 32 Did not complete the Math process needed to display data readings. Math Completion Error Did not receive the three sets of data readings from the CT strip sensor board. Strip Sync. Error Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 33 Each panelboard points list is the same as for Each panelboard points list is the same as for others of the same type. others of the same type. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 34 The Digital Points section is found after the Analog Points section. Digital 1 Digital 1 Subfeed 1 CB Aux Status (1 point) Relay 1 Relay 1 Relay 1 (1 Relay 1 digital point) Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 35 5. Select MODBUS or SNMP tab. 6. Select POINTS’ LIST button. Points List is downloaded as .zip file. 7. Select PL.zip file. 8. File is unzipped to two files as shown. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 36 Customer Sensor Board Connections Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 37 Update options and some setup screen command buttons are greyed out for guest users to show that they cannot make changes or access the screen. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 38 The system is shipped with a default administrator user ID = Admin and password = Admin. At first login, the Administrator should change the password and save it. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 39 Add User. To delete a user, select a user name from the drop-down list, select Delete User, and confirm the deletion. Add New User follows the same format. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 40 Not all names can be changed. Scroll through the Name list using NEXT and PREVIOUS buttons. Unlike many other screens, changes are not automatically saved. You must select SAVE to implement and save changes. Figure 18. NAMES Screen, Changing Banner Name Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 41 User Login Time Out: How long the Monitor will wait with no operator input before logging the user out. This only affects logged-in users, hence only administrators. Guest users do not log in and are not affected. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 42: Home Screen

    Figure 20. GENERAL Screen, BASIC Tab, Zero Fault Alarm in Alarm Header Zero Fault Alarm Monitor • LOAD DEFAULT loads the parameters created in manufacturing and shipped with the unit. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 43 NTP Service: When this check box is selected, the date/time will set automatically according to the Network Time Protocol Service and the date and time user input boxes will disappear. See for details. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 44 Setup Figure 22. GENERAL Screen: DATE/TIME — NTP Service Selected Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 45 3.2 Network Connections. Select the Setup icon in the banner, then select the Menu icon , select NETWORK/ PROTOCOLS. (See Figure 23). Figure 23. NETWORK/PROTOCOLS, Menu Option Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 46 Changes are not automatically saved. Select SAVE CHANGES. After saving, your Infinity 2 Monitor will reboot with these network parameters. LOAD DEFAULT loads network information created in manufacturing and shipped with the unit. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 47 Tab: If you are using SNMP you must also select the SNMP tab to set up additional SNMP parameters. V1/V2 Communities • : Enter your Get, Set, and Trap Communities. Figure 25. Setup: NETWORK/PROTOCOLS, V1/V2 Communities Tab Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 48 – Define the addresses of up to (3) three trap servers and individually enable the server(s). Figure 26. Setup: NETWORK/PROTOCOLS, Trap Settings Tab Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 49 Select Algorithm using the drop-down list. ○ Enter Password. ○ – Specify Encryption : Select Algorithm using the drop-down list. ○ Enter Password. ○ Figure 27. Setup: NETWORK/PROTOCOLS, V3 Settings Tab Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 50 Select POINTS LIST to download the SNMP MIB, which must be done from a browser. (See also paragraph 4.4.1 Downloading the Modbus Points List and SNMP MIB.) NOTE After pressing the Save Changes button, the monitor will reboot. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 51 Specify a Unit ID. Infinity 2 returns this user-specified ID in response to receiving Modbus function code • Select TCP Service to enable. Uncheck to stop the Modbus TCP Service. Reboot is required to Enable/Disable Service. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 52 Figure 30. Setup: NETWORK/PROTOCOLS, Modbus Tab, Reboot Message • Select POINTS LIST to download the Modbus points list for your unit. See also parapgraph 4.4.1 Downloading the Modbus Points List and SNMP MIB. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 53 Alarm limits are set and Alarm check boxes are greyed out if you are not individually for all logged in (as administrator). sensors or sensor boards in the Sensors List. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 54 Zero, showing that a circuit that previously measured at least 3A has measured < 0.5A. Zero alert levels cannot be adjusted. You can apply these alerts to all circuits uniformly or customize alerts by individual circuit. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 55 If you do not check All, values can be changed individually by circuit. You can set typical circuit parameters using All, then specify parameters for individual circuits as needed. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 56 first column propagate to all circuits. You can then change any circuit value individually. The last value you entered is highlighted in green if the change was successful. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 57 D1-D8 correspond to the D1-D8 Unassigned digital inputs are named as Extra, connections on the Digital Inputs with its connection number in parentheses: Options board. Extra (D6) Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 58 Thermal Over Temp = Alarm Temperature Level reached on transformer (may cause shutdown) EPO (Emergency Power Off) Remote EPO CB Trip Note: when CB Trip is checked, the main input circuit breaker has been tripped. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 59 Event Log. There are no relay status indicators on the HOME screen 1-line. Figure 37. Relay Screen A check mark indicates that the relay has been activated. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 60 Setup Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 61: Alarms

    If Panel has no Select to display Voltage Sensor: Voltage and (S), panelboard Input Voltage Select to display Current Sensor: has no CT sensor Transformer strip. Output Voltage and Current Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 62 Circuit breakers show open/closed status only. Subfeeds Select item from list to display its status screeen. Subfeed 1 Subfeed 2 Subfeed 3 Subfeeds Subfeed 4 Subfeed 5 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 63: Figure 40. Current Sensor Screens

    Metrics options Current (A), Demand, Max Demand, Min, Max, and Crest Factor (CF) Power Metrics screen with KW, Demand KW, Max Demand, KVA, KVAR, PF, and KWH. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 64: Alarm Notification

    Red = Above alarm limit Current/Power Screen by circuit (CKT): Current(A) Load (% of Breaker Rating) Power(KW) Power(KVA) Power(KVAR) Power Factor(PF) Circuit Status: –Good (Green) – Warning (Orange) –Alarm (Red) Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 65: Figure 42. Panelboard Screens (Part 2)

    Alarm: current exceeded alarm level (color code=red) • Warning: current exceeded warning level (color code=orange) • Zero: current fell to ≤ 0.5A after first measuring ≥ 3A (color code=orange) Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 66: Figure 43. Clear Meters

    Relays, see Relay 1, Relay 2, etc., Sensor Status screen (Figure 37). Digital Inputs status for circuit breakers with aux contacts is shown on the HOME screen (Figure 38). Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 67: Alarm Screen

    An alarm will never occur more than once on the Active or History list. However, if an alarm is raised multiple times, each occurrence will be listed in the Log. See paragraph 6.5 Log Events Screen. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 68: Figure 44. Active Alarms Vs. Alarm History

    Alarm History until removed. Select Garbage Can icon to clear the Alarm History. (Alarms cannot be individually cleared.) You must be logged in to clear the Alarm History. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 69: Figure 45. Log Events Screen

    To clear the Log, select the Reverse time- Garbage Can icon. You must display order. be logged into clear the Log. Select Event Log Icon Scroll buttons to view the Log Screen. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 70 Operation: Monitoring Your System Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 71 Sensor Board drop-down list. Measure circuit value. Enter correct measurement in ‘Calibrate to:’ field. On panel boards, you can scroll the circuit display using NEXT or PREVIOUS button. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 72 (so that the box “loses focus”). The box will turn green if calibration is successful, but red if not successful. Enter calibrated measurement. Close pop-up when you are done. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 73: Figure 46. Ct Fix Positions On Panelboard Ct Strip

    Identify the failing CT and panelboard CT strip. Log in to Infinity Monitoring System. Select the Tools button to bring up Sensor Board screen. Select the Menu button to display Menu Options. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 74 In this example, a split-core CT will be connected to CT Fix 1 position to substitute for CT2. CT Fix screen shows CT Fix 1 position in use for CT2. Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 75 CT Fix positions are as follows: • Upper strips (CT Fix 1=Top, 2=Middle, 3= Bottom) Lower strips (CT Fix 1=Bottom, 2=Middle, 3=Top) CT Fix 2 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 76 Maintenance Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01...
  • Page 77 C C h h a a p p t t e e r r 8 8 B B i i b b l l i i o o g g r r a a p p h h y y This manual and other product documentation for the Eaton Infinity Monitoring System can be downloaded from the product page on the Eaton website: https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-pdi-wavestar-...
  • Page 78 P-16400110601 P-164001106 01...