Durant Installation and Operation Manual Number 57750-900-03 Eclipse Series Pulse Input Flow Totalizers Flow Ratemeters Flow Batch Controls Models: 5775X-40X - Totalizer w/Rate 5775X-41X - Batch Control Durant PG M View Edit Start Stop BA TC H Enter Reset Durant ®...
Page 3
DESCRIPTION cont. Eclipse Flow Model Numbers 5775X-4XX Power Supply Output Option 0 = DC (9-30 VDC) 0 = No Option 1 = AC (85-265 VAC) 1 = Dual Relays (Standard on Batch) 2 = Analog Output (4-20mA & 0-10V 3 = Dual Relays & Analog Output 4 = RS-485 Communications Input / Function 5 = Dual Relays &...
Page 4
DESCRIPTION cont. Six digit Durant Display Program Mode Indicating P G M View Edit Reset Enter Four Input Keys...
Page 5
DESCRIPTION cont. Durant Relay 1 Pulses In P GM View Edit Start Stop BA T CH Enter Reset Flowmeter Valve Flow...
Page 6
DESCRIPTION cont. Durant Relay 1 Out Relay 2 Out Pulses In P GM View Edit Start Stop Enter B A T CH Reset Dribble Valve Flowmeter Flow Main Valve...
Page 7
DESCRIPTION cont. Six digit Durant Display P GM View Edit Start Stop Program Enter Reset BA TCH Mode Indicating Four Input Keys...
Page 11
MOUNTING Durant PG M View Edit Start Stop Enter Reset B A TC H 4.04 3.622 +/- .031 [92.00] Panel Cutout Max. Panel Thickness .190 [4.83]...
Page 12
WIRING WIRING AND DIP SWITCHES Analog DIP Switch RS485 Relay Communications Output Output Durant ® Power Input Count Input 2 Terminals for DC Powered Units Control Input 3 Terminals for AC Powered Units...
Page 13
WIRING cont. Durant ® Power In No Internal Fuse 9-30 VDC External Fuse Size 12 VA U.S. European 2 AMP, 50 V T2A, 50 V Time Delay Time Delay Durant ® No Internal Fuse Power In External Fuse Size 85-265 VAC U.S.
Page 15
WIRING cont. Durant ® DIP Switch Position 3 +12 VDC Out Flowmeter Input Inhibit Input Ground 2 Wire MAG Pickup Contact (Reed Switch, etc.) COMMON COMMON DIP 3 ON DIP 2 ON DIP 1 ON DIP 1 OFF Single Ended Mag Pickup Fast Response (>50 Hz) Slow Response (<50 Hz)
Page 23
PROGRAMMING cont. View Enter View Enter View Enter...
Page 24
PROGRAMMING cont. V ie w V ie w Hold Hold E n te r E n te r press press to scroll up to scroll down View Edit Enter View Edit Enter View Enter...
Page 48
DIAGNOSTICS cont. Durant ® Power Edit Start Edit Start Durant Edit Start Power...
Page 49
DIAGNOSTICS cont. / SPECIFICATIONS Test Key Unit Response View View/Enter Display shows software revision number Enter Edit Edit/Right Arrow All display segments and the program LED will turn OFF, and the analog output will go to maximum values (20 mA and 10V). Start Up Arrow Each display digit will turn ON, one at...
Page 52
The information included herein is believed to be accurate and reliable; however no responsi- bility is assumed by Eaton Corp., for its use; nor for any infringements of patents or other rights of third parties which may result from its use.
Page 53
Durant 901 S. 12th Street Watertown, WI 53094 800-540-9242 920-261-4070 Fax: 920-261-9097 www.durant.com...