Understanding The % Of Load Bar; Of Load Segment Table - Eaton IQ 100 series User & Installation Manual

Hide thumbs Also See for IQ 100 series:
Table of Contents

Advertisement

Understanding the % of Load Bar

The 10-segment LED bar graph at the bottom left of the IQ 100 Series front panel provides a graphic
representation of Amps. The segments light according to the load, as shown in the % Load Segment
Table below.
When the Load is over 120% of Full Load, all segments flash "On" (1.5 secs) and "Off" (0.5 secs).

% of Load Segment Table

Segments
none
1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
All Blink
User and Installation Manual IM02601003E - July 2010 www.eaton.com
IQ 100 Series ((130/140/150) Meter
Programming the Meter Using the Front Panel
Load >= % Full Load
no load
1%
15%
30%
45%
60%
72%
84%
96%
108%
120%
>120%
53