Programming the IQ 100 Series Meter Using Software

Overview

The IQ 100 Series meter can be configured using either the meter Face Buttons (Menu, Enter, Down
and Right) or Eaton Meter Configuration Software. To connect to the meter for software configuration,
use the RS485 port, if equipped, on the back panel of the meter.
The IQ 100 Series Transducer must be configured with the Eaton Meter Configuration Software, using
the RS485 port, since it does not have a front panel.
This chapter contains instructions for programming the meter and Transducer using software.

Connecting to the IQ 100 Series Meter/Transducer

1. Open Eaton Meter Configuration Software.
2. Click the Connect icon on the Title bar or
Connection>Quick Connect.
3. If you are connecting to the meter through your PC:
a. Make sure the Serial Port radio button is selected.
b. Enter Device Address (1-249).
c. Select Baud Rate from the pull-down menu.
d. Select the port you are using from the pull-down menu. The
Available Ports/All Ports radio buttons determine which port
selections the menu displays.
e. Select Modbus RTU from the Protocol pull-down menu.
f. Select Flow Control: None or Hardware.
g. Select Echo Mode: No Echo or Static Echo.
If you are connecting to the meter through the Power Xpert® Gateway:
a. Make sure the Network radio button is selected.
b. Enter Device Address (1-247).
c. Enter the Gateway's IP Address.
d. Enter Network Port.
e. Protocol defaults to Modbus TCP.
4. Click the Connect button. You will see the Device Status
screen, shown below on the right.
NOTE for IQ 100 Series Transducer:
When the Transducer is powered up, for 10
seconds you can connect to the meter using the
Factory Initial Default Settings (even if the Device
Profile has been changed). After 10 seconds,
the Device Profile reverts to the actual Device
Profile in use.
Factory Initial Default Settings
Baud Rate:
Port:
Protocol:
9600
COM1
Modbus RTU
User and Installation Manual IM02601003E - July 2010 www.eaton.com
IQ 100 Series ((130/140/150) Meter
Programming the IQ 100 Series Meter Using Software
55