Product Specifications; Regulatory/Standards Compliance - Eaton Cutler-Hammer IQ 300 Series Instructions For Installation, Operation And Maintenance

Table of Contents

Advertisement

2.4.3.1 Fusing IQ 300 Power Supply
External fuses should be installed in the IQ 300 power supply lines, near the IQ 300
Base Module. 600 volt ½ Ampere BUSS type KTK-R-1/2 Fast Acting or equivalent
fuses are recommended for the IQ 300 Base PS1 and PS2 power supply lines.
2.4.3.2 Fusing Potential Transformers
External fuses should be installed in the potential transformer lines as specified in
the National Electric Code for the specific application.
2.5
PRODUCT
SPECIFICATIONS
Refer to tables 2.1
through 2.5 for all IQ
300 specifications.
2.5.1
Regulatory/
Standards
Compliance
The IQ 300 series
meets UL, CSA and
CE requirements.
Effective Date: 2/04
For more information visit:
IQ 300
Table 2.1 IQ 300 Safety Specifications
IEC 1010-1 (1990) Incl. Amend 1&2 (1995)
EN61010-1 (1993)
CSA C22.2 #1010.1 (1992)
UL3111
Emissions
FCC Part 15 Class A
CISPR 11 (1990) / EN55011 (1991) Group 1 Class A
Immunity
Electrostatic Discharge
EN61000-4-2 (1995) / EN61000-6-2 (1999) 4kV CD
Electrical Fast Transient
EN61000-4-4 (1995) / EN61000-6-2 (1999) 2kV PL
Radiated Immunity
EN61000-4-3 (1999) / EN61000-6-2 (1999) 10V/m
Conducted Immunity
EN61000-4-6 (1999) / EN61000-6-2 (1999) 10Vrms
Power Frequency Magnetic Field
EN61000-4-8 (1995) / EN62000-6-2 (1999) 30 A/m
Surge Voltage
EN61000-4-5 / EN61000-6-2 (1999)
Voltage Dips
EN61000-4-11 / EN61000-6-2 (1999)
www.cutler-hammer.eaton.com
Effective Date: 2/04
Safety
EMC
IL17574C
Page 2-9
8kV AD
2kV SL
Page 2-9