ABB ControlMaster CM10 User Manual page 99

Universal process controllers
Hide thumbs Also See for ControlMaster CM10:
Table of Contents

Advertisement

ControlMaster CM10, CM30 and CM50
Universal process controllers,
Number /
Icon
Message
230.010
(228.011)
WV 1 (2) Failed
234.008
(232.009)
PFB 1 (2) Failed
216.016
NV Error Proc Bd
214.017
NV Error Main Bd
212.018
NV Error Opt Bd 1
210.019
NV Error Opt Bd 2
Table 7.1 Diagnostic Messages (Continued)
IM/CM/S–EN Rev. R
1
1
1
/
,
/
and
/
DIN
8
4
2
Possible Cause
Problem with input assigned to Loop 1 (2) wild variable.
Broken sensor leads, defective input source or input
signal out of permitted range.
Problem with input assigned to Loop 1 (2) position
feedback. Broken sensor leads, defective input source
or input signal out of permitted range.
Failure of non-volatile memory on processor / display
board or permanent corruption of its data .
Failure of non-volatile memory on main board or
permanent corruption of its data.
Failure of non-volatile memory on option board 1 or
permanent corruption of its data.
Failure of non-volatile memory on option board 2 or
permanent corruption of its data.
Suggested Action
Check wiring. Check input source.
Check if input signal is outside permitted limits
Check wiring. Check input source.
Check if input signal is outside permitted limits
Check all configuration parameters and correct any
errors. Acknowledge error.
If problem persists contact local service organization.
Check calibration of AIN1, AIN2 and AO1. Recalibrate if
necessary. Acknowledge error.
If problem persists contact local service organization.
Check calibration of AO2, AIN 3 and AIN4 (CM50 only).
Recalibrate If necessary. Acknowledge error.
If problem persists contact local service organization.
Check calibration of AO2, AIN 3 and AIN4.
Recalibrate If necessary. Acknowledge error.
If problem persists contact local service organization.