ControlMaster CM10, CM30 and CM50
Universal process controllers,
...Device Setup / ...Initial Setup
Instrument Tag
Mains Freq
Config Action
Continue
Hold
Inactive
Custom Template
Reset to Defaults
IM/CM/S–EN Rev. R
1
1
1
/
,
/
and
/
DIN
8
4
2
A 16-character alphanumeric tag, displayed on Operator pages.
Used to set the internal filters to reduce mains power frequency interference.
The Config Action parameter is used to determine how the controller and controller outputs
behave when the Advanced level is entered – see page 36.
The controller continues to operate as in Operator level. Outputs continue to operate as
normal.
Puts the controller into Manual control mode. When the Advanced level is exited, the
controller returns to the pre-Configuration mode of operation. Digital, relay and analog
outputs are held at their value / state when Configuration mode is entered.
Puts the controller into Manual control mode. When the Advanced level is exited, the controller
returns to the pre-configuration mode of operation.
Digital and relay outputs are turned off. Analog outputs are set to 0 mA.
If this parameter is enabled, it enables the internal function blocks to be re-linked to create
custom configurations for special application requirements.
These sources are configured in Device Setup / Custom Config – see page 38.
Resets all configuration parameters to their default values.
7 Advanced Level
37