ControlMaster CM10, CM30 and CM50
Universal process controllers,
Control parameters
Proportional band *
0.0 to 999.9 %
Integral *
0 to 10000 s
Derivative *
0.0 to 999.9 s
Manual Reset
0.0 to 100.0 %
Setpoints
Local
CM10
2, selectable via digital inputs or front panel
CM30 / CM50
4, selectable via digital inputs or front panel
Remote
selectable via digital input or front panel
keys
Autotune
On-demand calculation of control settings
Process alarms
Number
8
Types
High / Low process and High / Low latch
Source
Fully configurable (for example, PV, analog
input, math block inbuilt, OP control loop
deviation)
Hysteresis
Level and time
Alarm enable
Enable / disable of individual alarms via a
digital signal
* 3 sets of PID parameters when used with Gain Scheduling facility
IM/CM/S–EN Rev. R
1
1
1
/
,
/
and
/
DIN
8
4
2
Acknowledgement
Via front panel keys or digital signals
Real-time alarms **
Number
2
Programmable
Time
Day
Duration
Bank control **
Number of outputs 6
Wear levelling
Rotate or FIFO
Math blocks **
Number
8
Operators
+, –, x , /
Average, Maximum, Minimum
High / Low / Median Select
Square root
Multiplexer
Delay timers **
Number
2
Programmable
Delay
Duration
** Functionality level 'Standard' and above only