ControlMaster CM10, CM30 and CM50
Universal process controllers,
Communications
For MODBUS and Ethernet communications see separate User
Guide (IM/CM/C–EN).
IrDA configuration port (standard)
Baud rate
up to 115 kBaud
Distance
up to 1 m (3 ft.)
Functions
Firmware upgrade
configuration upload / download
EMC
Emissions & immunity
Meets requirements of IEC61326 for an Industrial Environment
Environmental
Operating temperature range
0 to 55 °C (32 to 131 °F)*
Operating humidity range
5 to 95 %RH (non-condensing)
Storage temperature range
–20 to 70 °C (–4 to 158 °F)
*Restrictions may apply, refer to relay specification
114
1
1
1
/
,
/
and
/
DIN
8
4
2
Enclosure sealing
Front face
IP66 / NEMA 4X
Rest of enclosure
IP20
Vibration
Conforms to EN60068-2-6
Safety
Approvals and certifications
EN61010-1
cULus
General safety
Pollution category 2
Insulation category 2
Isolation (to inputs)
Analog I/Ps
Tx PSU
Analog O/P 1
Analog O/P 2
Key
= Isolation
10 Specification
Comms
Relays
CPU
Digital I/O
Mains Supply
IM/CM/S–EN Rev. R