ControlMaster CM10, CM30 and CM50
Universal process controllers,
...Control / ...Loop 1 Output
Manual 1 (2)
Config O/P
A/M Toggle
A/M Output
Last Auto O/P
Man – 0%
Man – 100%
Config Value
A/M Config O/P
IM/CM/S–EN Rev. R
1
1
1
/
,
/
and
/
DIN
8
4
2
Used when Manual 1 (2) Output is set to Config Value.
The source required to toggle between A/M (Auto / Manual) control
modes. When the digital signal is high, the controller is locked in
Manual control mode (the front panel controls [see page 5] and
other digital select signals have no effect). When the digital signal is
low, Auto control mode is selected. When in the low state, either the
front panel controls or edge-triggered digital signals can be used to
put the controller into Manual control mode.
Sets the (manual) output value when the controller is put into Manual mode using A/M Toggle
source
Holds the output at its value prior to switching to Manual control mode.
Sets the output to 0 %.
Sets the output to 100 %.
Sets the output to the value set in A/M Config O/P.
Used when A/M Output is set to Config Value.
7 Advanced Level
Manual
Auto
59