ControlMaster CM10, CM30 and CM50
Universal process controllers,
RTD
Maximum Range
–200 to 600
Pt100
(–325 to 1100)
Linear Inputs
Analog Input
Millivolts
Milliamps
0 to 45 mA (CM10 and CM30)
0 to 50 mA (CM50)
Volts
Resistance  (low)
Resistance  (high)
Sample Interval
125 ms per sample
112
1
1
1
/
,
/
and
/
8
4
2
Accuracy
°C (°F)
(% of reading)
0.1 % or ±0.5 °C
(0.9 °F)
Standard
Accuracy
(% of reading)
0 to 150 mV
0.1 % or ±20 µV
0.2 % or ±4 µA
0 to 25 V
0.2 % or ±20 mV
0 to 550 
0.2 % or ±0.1
0 to 10 k
0.5 % or ±10
DIN
Digital Inputs
Type
Minimum pulse
duration
Frequency input*
Frequency range
1-signal
0-signal
*For use with devices with open collector outputs
10 Specification
Volt-free or 24 V
Analog inputs 1 and 2:
Single input configured – 250 ms
Both inputs configured as analog or
digital – 500 ms
Analog inputs 3 and 4 (not CM10):
Single inputs configured – 250 ms
Both inputs configured as analog or
digital – 500 ms
Consider analog inputs 1 / 2 and 3 / 4
independently
0 to 6000 Hz
15 to 30 V
–3 to 5 V
IM/CM/S–EN Rev. R