ControlMaster CM10, CM30 and CM50
Universal process controllers,
... Input/Output / ...Analog Input 1 (4)
Pulse Units
Pulse / Unit
Broken Sensor
None
Automatic
Upscale
Downscale
46
1
1
1
/
,
/
and
/
DIN
8
4
2
Selects the unit of measure for the pulse input type.
Sets the number of pulses required to represent 1 pulse unit (as set above), for example, if
Pulse Units = Kl and Pulse / Unit = 10.00000000, each pulse represents 0.1 Kl,
10 pulses = 1 Kl.
If an input failure occurs, the input value can be configured to drive in a set direction.
No action taken.
If the value of failed input is below Eng Low (see page 45), the input value is driven to the
minimum downscale value; otherwise it is driven to the maximum upscale value.
The input is driven to the maximum upscale value.
The input is driven to the minimum downscale value.
7 Advanced Level
IM/CM/S–EN Rev. R