ABB ControlMaster CM10 User Manual page 115

Universal process controllers
Hide thumbs Also See for ControlMaster CM10:
Table of Contents

Advertisement

ControlMaster CM10, CM30 and CM50
Universal process controllers,
Outputs
Controls / retransmission outputs
Number
2 (1 standard, 1 optional)
Type
Configurable as analog or digital pulse
Isolation
Galvanically isolated from the rest of the circuitry,
500 V for 1 minute
Analog range
0 to 20 mA programmable
750 Max.
Load
Accuracy
0.25 % of output or ± 10µA
Relays
Number
CM10 / CM30: 4 (1 standard, 3 optional)
CM50: 4 (2 standard, 2 optional)
Type
CM10, CM30: Standard with changeover
contacts. Optional contacts selectable as N/O
or N/C (by jumper)
CM50: Selectable as N/O or N/C (by jumper)
Contact ratings
CM10:
Relay 1:
Relays 2, 3, 4:
Relays 2, 3, 4:
CM30, CM50:
5 A, 240 V
Update rate
125 ms
IM/CM/S–EN Rev. R
1
1
1
/
,
/
and
/
DIN
8
4
2
5 A, 240 V
5 A, 240 V (max. ambient
40 °C (104 °F)
2 A, 240 V (max. ambient
55 °C (131 °F)
Digital input / output
CM10
2 (optional)
CM30 / CM50 6 (2 standard, 4 optional)
Type
User-programmable as input or output
Minimum input pulse duration – 125 ms
Input
– volt-free or 24 V DC
– 1-signal: 15 to 30 V
– 0-signal: –3 to 5 V
– Conforms to IEC 61131-2
Output
– Open collector output
– 30 V, 100 mA max. switched
– Conforms to IEC 61131-2
Update rate
125 ms
2-Wire transmitter power supply
CM10
1 (standard)
CM30 / CM50
2 (1 standard, 1 optional)
Voltage
24 V DC
Drive
2 loops 45 mA max.
10 Specification
113

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Controlmaster cm30Controlmaster cm50

Table of Contents