Configures the control output follow a tracking signal when in Auto control mode. In Manual control
mode, the output can be adjusted as normal. If the Slew Rate (see page 60) function is enabled,
switching from Manual to Auto is bumpless. If the value set by the tracking signal differs to the manual
setting, the output ramps to its expected auto value at the speed set in the Slew Rate. If the Signal
Source is set to None
tracking is disabled and the normal PID output is provided as the control output.
,
Sets the source of the signal required to be tracked by the output in Auto control mode.
If set to None, output tracking is disabled.
Selects the type of object tracking.
Control output = tracking signal when in Auto control mode.
Control output = tracking signal + change in PID output, when in Auto control mode.
When enable source is active, control output = tracking signal when in Auto control mode.
When enable source is active and the controller is in Auto control mode, the control output =
tracking signal + change in PID output.
Sets the digital signal to enable output tracking.
Note. Applicable only if Mode is When Enabled or When Enabled + OP.