ControlMaster CM10, CM30 and CM50
Universal process controllers,
Number /
Icon
Message
070.040
(066.041)
Tuner 1 (2) Abort
094.034
(090.035)
Valve 1 (2) Sticking
168.026 (166.027)
(164.028)
Tuner 1
Phase 1..3
160.030
(158.031)
156.032)
Tuner 2
Phase 1..3
162.029
(154.033)
Tuner 1 (2) Pass
178.025
In Configuration
Table 7.1 Diagnostic Messages (Continued)
IM/CM/S–EN Rev. R
1
1
1
/
,
/
and
/
DIN
8
4
2
Possible Cause
Autotune has been aborted by the user.
Motorized valve travel time is significantly slower than
configured time.
Autotune is in progress. See page 29 for details of each
phase.
Autotune is in progress. See page 29 for details of each
phase.
Autotune has completed successfully and calculated
new control parameters.
The device is currently in the configuration mode.
Suggested Action
Check valve to identify reason for sticking.
Check correct travel time is entered in configuration.
Autotune can be aborted if required by selecting Manual
control mode.
Autotune can be aborted if required by selecting Manual
control mode.
Acknowledge diagnostic
This is for use with remote access via digital
communications.