DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL

6.2.4 How to detect transmission errors

A timeout occurred for the transmission monitoring time (timer 2).
Designated number of transmission data was larger than the size that could be stored in the
transmission area.
OUTPUT instruction
Complete device + 1
6 - 30
This section explains how to detect errors that may occur when sending data to the
external device.
The following items are considered as the primary causes of errors that may occur
during data transmission.
Cause of reception error
(1) Confirmation using the sequence program
(a) Detecting a transmission error
1) The following device and input signal turn ON.
• OUTPUT instruction complete device + 1
• ERR. occurrence (XE/XF)
2) The transmission error code can be checked using the OUTPUT
instruction control data ((S1) + 1).
Or, it can be checked by reading the data transmission result (address:
257
/267
H
For details on how to check the error code contents and corrective
actions, see Chapter 11.
(b) How to turn off the ERR LED and clear the error code (see Section 11.1.2)
1) To turn off only the ERR LED, write "1" to the LED off, Communication
error clear request (address: 0
2) To turn off the ERR LED and clear the error code, turn ON the ERR.
clear request (YE/YF).
(Example) To perform the ERR LED OFF and the error code clear on the
CH1 side
).
H
/1
H
MELSEC-Q
Reference section
User's Manual (Application)
Section 6.2.2
).
H
6 - 30