11 TROUBLESHOOTING
Error code
Error
(Hexa-
decimal)
7F91
H
to
7F96
H
7F98
H
to
7F9A
H
7F9D
H
7F9E
H
7FA0
H
to
7FA3
H
7FA8
H
7FAA
H
System error
to
7FAD
H
7FAF
H
to
7FB2
H
7FB5
H
7FB6
H
7FB8
H
to
7FBC
H
7FC0
H
to
7FC4
H
Protocol setting data
7FC8
H
error
7FC9
H
to
System error
7FCF
H
7FD0
H
Refer to the error code list for use of the modem function, and take corrective action. (Refer to Section 11.2.3.)
to
7FE5
H
7FE6
H
7FE7
H
Processing disabled
7FE8
H
Refer to the error code list for use of the modem function, and take corrective action. (Refer to Section 11.2.3.)
7FE9
H
7FEF
Switch setting error
H
11 - 28
Description
The OS of the Q series C24 detected
some error.
There is an error in the protocol setting
that was edited in GX Configurator-SC
(Pre-defined protocol support function).
The protocol setting data written to the
Q series C24N includes unsupported
function data.
The protocol setting data written to the
Q series C24N is corrupted.
The OS of the Q series C24 detected
some error.
Remote passwords do not match.
The remote password is not registered.
The remote password processing
command was received on the interface
side where the modem function is not
used.
The GX Developer connection is
selected in the communication protocol
setting on the corresponding CH.
The number of remote password
disagreements exceeded the value
designated at the address 200D
There is an error in the switch setting by
the GX Developer
Signal
Corrective action
name
1
Identify the incorrectly edited protocol in
Protocol setting data error information
(buffer memory: 4086
correct the setting data, and write them
again to the Q series C24N.
Check the version of the Q series C24N
CHn
to confirm the supported functions. Use
the pre-defined protocol function within
ERR.
the range of supported functions.
Write the protocol setting data again to
the Q series C24N, and execute the
CPRTCL instruction.
If this error persists even after rewriting,
replace the module.
1
Check the remote password and
communicate again.
A remote password processing
command is not necessary when a
remote password is not registered.
Perform a remote password unlock
CHn
processing through GX Developer.
ERR.
Alternatively, change the
communication protocol setting of the
corresponding CH to the MC protocol.
Clear the storage area of the
CHn
accumulated count of unlock process
abnormal completion processing
ERR.
.
H
(address: 22FC
Write CPU to the parameter and reboot
CHn
after correcting the setting value for the
ERR.
switch.
MELSEC-Q
MC
Proce-
to 4089
),
H
H
) to 0.
H
Protocol
Non
Bidire-
Pre-
ctional
defined
dure
11 - 28