10 DEDICATED INSTRUCTIONS

10.5 G(P).BIDOUT

Set
Internal device
data
(System, user)
Bit
Word
(S1)
(S2)
(D)
[Instruction
code]
G.BIDOUT
GP.BIDOUT
Set data
Set data
Un
(S1)
(S2)
(D)
Control data
Device
(S1) + 0
Transmission channel
(S1) + 1
Transmission result
Transmission data count • Set the transmission data count.
(S1) + 2
10 - 15
Data can be sent using the bidirectional protocol.
Link direct device
J \
File register
Bit
[Executing
condition]
Command
Command
Start I/O signal of the module
(00 to FE: Top two-digit when I/O signals are expressed in 3-digit.)
Head number of the devices in which control data is stored.
Head number of the devices in which transmission data is stored.
Bit device number to be turned on at completion of execution.
The file register per local device and program cannot be used as the set data.
Item
• Set transmission channel
1: Channel 1 (CH1 side)
2: Channel 2 (CH2 side)
• Transmission result by a BIDOUT instruction are
stored.
0:
Other than 0: Error code
1 For error codes relating to abnormal completion, see Chapter 11.
2 When setting "Word/byte units designation" by GX Configurator-SC, set the number
of bytes when bytes are designated and set the number of words when words are
designated.
3 The settings are done by either of the following:
• User
: Data set by the user before executing the BIDOUT instructions.
• System : The programmable controller CPU stores the execution result of the
BIDOUT instructions.
Applicable device
Intelligent function
module device
U \G
Word
Un
G.BIDOUT
Un
GP.BIDOUT
Description
Set data
Normal
1
2
MELSEC-Q
Index register
Constant
Zn
(S1)
(S2)
(D)
(S1)
(S2)
(D)
Set by
User
User, system
User
System
Setting range
1, 2
1 or more
Others
Data type
BIN16 bit
Device name
Bit
3
Set by
User
System
User
10 - 15