Origin Search Function; Input Time Constant Setting For The General-Purpose Inputs - Omron CJ1M-CPU21 Operation Manual

Cj-series built-in i/o cpu units
Hide thumbs Also See for CJ1M-CPU21:
Table of Contents

Advertisement

PLC Setup Settings
Input Operation Setting for IN3
Programming
Settings
Console setting
address
Word
Bits
60
12 to 15 0 hex:
Normal (General-
purpose input)
1 hex:
Interrupt (Inter-
rupt input) (See
note.)
2 hex:
Quick (Quick-
response input)

Input Time Constant Setting for the General-purpose Inputs

Programming
Settings
Console setting
address
Word
Bits
61
00 to 07 00 hex: Default
(8 ms)
10 hex: 0 ms
(no filter)
11 hex: 0.5 ms
12 hex: 1 ms
13 hex: 2 ms
14 hex: 4 ms
15 hex: 8 ms
16 hex: 16 ms
17 hex: 32 ms
4-2-2

Origin Search Function

Default
0 hex
Specifies the kind of input that is
being received at built-in input IN3
Note The input operation setting for
Note When IN3 is set as an interrupt input (1 hex), use the MSKS(690) instruction
to select direct mode or counter mode operation.
Default
0 hex
Specifies the input time constant for
general-purpose inputs IN0 to IN9.
Note This setting has no effect on
The following tables show the settings for the origin search function in the CX-
Programmer. These settings are for CJ1M CPU Units equipped with the built-
in I/O functions.
Note CX-Programmer Tabs
CX-Programmer Ver. 3.1 or lower: Define Origin Operation Settings Field of
Define Origin
CX-Programmer Ver. 3.2 or higher: Pulse Output 0
Function
IN3 is disabled when high-
speed counter 0 is being used
and the reset method is set to
Phase-Z signal + software
reset.
Function
inputs set as interrupt inputs,
quick-response
inputs,
high-speed counters.
Section 4-2
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When power is
turned ON
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When operation
starts
or
57