Specifications
3-1-2

Input Function Block Diagram

Analog input 1
A/D
Analog input 2
Same as above.
Analog input 3
Same as above.
Same as above.
Analog input 4
Analog input 5
Same as above.
Analog input 6
Same as above.
Analog input 7
Same as above.
Same as above.
Analog input 8
3-1-3

Input Specifications

Range: 1 to 5 V (4 to 20 mA)
82
Analog Input Unit
Mean value
processing
Input dis-
disabled
connection
detection
Mean value
processing
enabled
Note There are only four analog inputs for the CJ1W-AD041-V1.
If signals that are outside the specified range provided below are input, the
conversion values (16-bit binary data) used will be either the maximum or
minimum value.
Conversion value
1068 (20D0)
0FA0 (1F40)
0000 (0000)
FF38 (FE70)
Peak value
hold function
disabled
Peak value
hold function
enabled
1 V/4 mA
5 V/20 mA
5.2 V/20.8 mA
0.8 V/3.2 mA
Analog input signal
Section 3-1
CPU Unit
Special I/O
I/O
Unit Area
refresh
Conver-
sion value
for Analog
input 1
Resolution: 4,000
(Resolution: 8,000)