PLC Setup Settings

Pulse Output 1 Origin Detection Method

Programming
Settings
Console setting
address
Word
Bits
275
08 to 11 0 hex: Method 0
(Origin detection
method 0)
1 hex: Method 1
(Origin detection
method 1)
2 hex: Method 2
(Origin detection
method 2)

Pulse Output 1 Origin Search Operation Setting

Programming
Settings
Console setting
address
Word
Bits
275
04 to 07 0 hex:
Inverse 1 (Rever-
sal mode 1)
1 hex:
Inverse 2 (Rever-
sal mode 2)

Pulse Output 1 Origin Search Operating Mode

Programming
Settings
Console setting
address
Word
Bits
275
00 to 03 0 hex: Mode 0
1 hex: Mode 1
2 hex: Mode 2
Pulse Output 1 Undefine Origin Setting (CJ1M CPU Unit Ver. 2.0 Only)
Programming
Settings
Console setting
address
Word
Bits
286
12 to 15 0 hex: Hold
1 hex: Undefine

Pulse Output 1 Origin Input Signal Type

Programming
Settings
Console setting
address
Word
Bits
286
08 to 11 0 hex: NC
1 hex: NO
Default
Function
0 hex
Specifies the origin detection method
for pulse output 1.
Default
Function
0 hex
Specifies the origin search operation
for pulse output 1.
Default
Function
0 hex
Specifies the origin search mode for
pulse output 1.
Default
Function
0 hex
Specifies whether to hold the origin
setting when the CW/CCW limit input
signal is input during execution of an
origin search or pulse output function.
Default
Function
0 hex
Specifies whether the Origin Input
Signal for pulse output 1 is normally
closed or normally open.
Section 4-2
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When operation
starts
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When operation
starts
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When operation
starts
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When operation
starts
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When operation
starts
63

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1m-cpu23Cj1m-cpu22

Table of Contents