4) Setting the frequency using input voltage (0~10Vdc)
VI/II
+
:Voltage signal 0-10Vdc
CCA
-
[Parameter setting]
Set the "basic parameter frequency setting mode selection 1" parameter  to  .
In addition, set the "extended parameter analog input VI/II voltage/current
switching" parameter  to  (default setting
5) Setting the frequency using input voltage (0~±10Vdc)
The direction can be changed by switching between positive and negative signals.
+
RX
:Voltage signal 0~±10Vdc
-
CCA
[Parameter setting]
Set the "basic parameter frequency setting mode selection 1" parameter  to .
Note: Set reference frequency priority selection  to  (/ terminal switching, default setting).
Changing the settings of two speed command parameters at a time, refer to Section 6.6.
[Example of setting: To set the frequency by applying a current of 4(0)-20mAdc via the VI/II terminal.]
Key operated
LED display

MODE

ENT

ENT
Voltage signal
Voltage signal (0~10V) for setting the operation frequency
 Refer to Section 7.3 for details of adjustment.
Voltage signal
Voltage signal (0~±10V) for setting the operation frequency
 Refer to Section 7.3 for details of adjustment.
Forward run
Reverse run
Displays the operation frequency. (Perform during operation stopped.)
(When standard monitor display selection =[Output

frequency])
Displays the first basic parameter "History function ()."
Press either the
Press the ENTER key to display the parameter setting (Default

setting:).

Press the
key to change the parameter to .
Press the ENTER key to save the changed parameter.  and the
parameter are displayed alternately.
C-5
60Hz
Frequency
0
0Vdc
.
)
60Hz
-10Vdc
60Hz
Operation
or
key to select "."
E6581386
10Vdc
3
+10Vdc