1) External connection
(1) Process value
DC:0~10V
6
2) Types of PID control interface
Process value (frequency) and feedback value can be combined as follows for the PID control of the VF-PS1.
(1)Process value(frequency setting)
Frequency setting mode selection /
:VI/II (voltage/current input)
:RR/S4 (potentiometer/voltage input)
:RX (voltage input)
:Operation panel input enabled (including LED/LCD
option input)
:2-wire RS485 communication input
:4-wire RS485 communication input
:Communication option input
:Optional AI1 (differential current input)
:Optional AI2 (voltage/current input)
:UP/DOWN frequency
:Optional RP pulse input
:Optional high-speed pulse input
Note 1: About the setting of and: Do not select the same terminal that is used feedback
terminal.
Note 2: The voltage/current changeover of the analog input VI/II and the option AI1 can be set by the parameter
 or 
Note 3: The reaching signal of the feedback value and the process value can be output.
The desired feedback input should be assigned to the unoccupied output terminal.
The detection width for reaching can be set by the parameter 
R
S
T
RR/S4
CCA
VI/II
(2) Feedback value DC:4~20mA
, 0:Voltage input (DC:0~10V)
If the feedback input is RR/S4 terminal: Function number 144,145
If the feedback input is VI/II terminal : Function number 146,147
If the feedback input is RX terminal
U
V
W
(2) Feedback value
PID control feedback control signal selection

:Deviation input (no feedback input)
:VI/II (voltage/current input)
:RR/S4 (potentiometer/voltage input)
:RX (voltage input)
:Optional AI1 (differential current input)
:Optional AI2 (voltage/current input)
: PG feedback option
1:current input (DC:4~20mA)
: Function number 148,149
F-32
E6581386
M
Pressure
transmitter
P