[23] Protection functions [2/4]
Communi
Title
cation
Function
No.
0606
OL reduction starting frequency


0608
Input phase failure detection mode selection

0609
Low current detection hysteresis width

0610
Low current trip selection
0611
Low current detection current


0612
Low current detection time
0613
Selection of short circuit detection at starting

0615
Overtorque trip selection

Overtorque detection level during power
0616

running
Overtorque detection level during

0617
regenerative braking

0618
Overtorque detection time

0619
Overtorque detection hysteresis

0620
Cooling fan control selection
0621
Cumulative operation time alarm setting


0622
Abnormal speed detection time

0623
Overspeed detection frequency upper band
0624
Overspeed detection frequency lower band

0625
Undervoltage detection level


0626
Overvoltage limit operation level

0627
Undervoltage trip selection

0629
Regenerative power ride-through control level

0631
Temperature detection
VI/II analog input wire breakage detection
0633

level
Adjustment range
0.0~60.0Hz
0:Disabled
1:Enabled
1~20%
0:No trip
1:Trip
0~100%
0~255 sec.
0:Each time (standard pulse)
1:Only one time after power is turned on
2:Each time (short pulse)
3.Only one time after power is turn on (short
pulse)
4:Each time (Extremely shot-time pulse)
5.Only one time after power is turn on (Extremely
shot-time pulse)
0:No trip
1:Trip
0~250%
0~250%
0.00~10.00 sec.
0~100%
0:Auto
1:Always ON
0.1~999.9 (x100h)
0.01~100.0 sec.
0.0:Disabled, 0.1~30.0Hz
0.0:Disabled, 0.1~30.0Hz
50~79%, 80: (auto mode)
100~150%
0:Disabled
1:Enabled
55~100%
0:Standard (120%-60 sec.)
1:Estimation of temperature
0:None
1~100%
Sensorless vector/PG feedback control (●:Effective, -:Ineffective)
Minimum
setting unit
Default
Write during
Vector
(Panel/Communi
setting
running
control
cation)
0.1/0.01
6.0
Enabled
●/●
1/1
1
Disabled
●/●
1/1
10
Enabled
●/●
1/1
0
Enabled
●/●
1/1
0
Enabled
●/●
1/1
0
Enabled
●/●
1/1
0
Disabled
●/●
1/1
0
Enabled
●/●
1/0.01
150
Enabled
●/●
1/0.01
150
Enabled
●/●
0.01/0.01
0.50
Enabled
●/●
1/0.01
10
Enabled
●/●
1/1
0
Enabled
●/●
0.1/0.1
610.0
Enabled
●/●
0.01/0.01
0.01
Enabled
●/●
●/●
0.1/0.01
0.0
Enabled
0.1/0.01
0.0
Enabled
●/●
1/1
80
Disabled
●/●
1/1
134
Disabled
●/●
1/1
0
Disabled
●/●
1/1
75
Disabled
●/●
1/1
0
Disabled
-
1/1
0
Enabled
●/●
PM
V/f Constant Reference
control
5. 14
6. 26. 6
6. 26. 7
6. 26. 7
6. 26. 7
6. 26. 7
6. 26. 8
6. 26. 9
6. 26. 9
6. 26. 9
6. 26. 9
6. 26. 9
6. 26. 10
6. 26. 11
6. 26. 12
6. 26. 12
6. 26. 12
6. 26. 14
6. 15. 2
6. 26. 14
6. 26. 15
-
-
5. 14
6. 26. 16