[23] Protection functions [2/4]
Communi
Title
cation
Function
No.
0606
OL reduction starting frequency
0608
Input phase failure detection mode selection
0609
Low current detection hysteresis width
0610
Low current trip selection
0611
Low current detection current
0612
Low current detection time
0613
Selection of short circuit detection at starting
0615
Overtorque trip selection
Overtorque detection level during power
0616
running
Overtorque detection level during
0617
regenerative braking
0618
Overtorque detection time
0619
Overtorque detection hysteresis
0620
Cooling fan control selection
0621
Cumulative operation time alarm setting
0622
Abnormal speed detection time
0623
Overspeed detection frequency upper band
0624
Overspeed detection frequency lower band
0625
Undervoltage detection level
0626
Overvoltage limit operation level
0627
Undervoltage trip selection
0629
Regenerative power ride-through control level
0631
Temperature detection
VI/II analog input wire breakage detection
0633
level
Adjustment range
0.0~60.0Hz
0:Disabled
1:Enabled
1~20%
0:No trip
1:Trip
0~100%
0~255 sec.
0:Each time (standard pulse)
1:Only one time after power is turned on
2:Each time (short pulse)
3.Only one time after power is turn on (short
pulse)
4:Each time (Extremely shot-time pulse)
5.Only one time after power is turn on (Extremely
shot-time pulse)
0:No trip
1:Trip
0~250%
0~250%
0.00~10.00 sec.
0~100%
0:Auto
1:Always ON
0.1~999.9 (x100h)
0.01~100.0 sec.
0.0:Disabled, 0.1~30.0Hz
0.0:Disabled, 0.1~30.0Hz
50~79%, 80: (auto mode)
100~150%
0:Disabled
1:Enabled
55~100%
0:Standard (120%-60 sec.)
1:Estimation of temperature
0:None
1~100%
Sensorless vector/PG feedback control (●:Effective, -:Ineffective)
Minimum
setting unit
Default
Write during
Vector
(Panel/Communi
setting
running
control
cation)
0.1/0.01
6.0
Enabled
●/●
1/1
1
Disabled
●/●
1/1
10
Enabled
●/●
1/1
0
Enabled
●/●
1/1
0
Enabled
●/●
1/1
0
Enabled
●/●
1/1
0
Disabled
●/●
1/1
0
Enabled
●/●
1/0.01
150
Enabled
●/●
1/0.01
150
Enabled
●/●
0.01/0.01
0.50
Enabled
●/●
1/0.01
10
Enabled
●/●
1/1
0
Enabled
●/●
0.1/0.1
610.0
Enabled
●/●
0.01/0.01
0.01
Enabled
●/●
●/●
0.1/0.01
0.0
Enabled
0.1/0.01
0.0
Enabled
●/●
1/1
80
Disabled
●/●
1/1
134
Disabled
●/●
1/1
0
Disabled
●/●
1/1
75
Disabled
●/●
1/1
0
Disabled
-
1/1
0
Enabled
●/●
PM
V/f Constant Reference
control
●
●
5. 14
●
●
6. 26. 6
●
●
6. 26. 7
●
●
6. 26. 7
●
●
6. 26. 7
●
●
6. 26. 7
●
●
6. 26. 8
●
●
6. 26. 9
●
●
6. 26. 9
●
●
6. 26. 9
●
●
6. 26. 9
●
●
6. 26. 9
●
●
6. 26. 10
●
●
6. 26. 11
●
●
6. 26. 12
●
●
6. 26. 12
●
●
6. 26. 12
●
●
6. 26. 14
●
●
6. 15. 2
●
●
6. 26. 14
●
●
6. 26. 15
-
-
5. 14
●
●
6. 26. 16